Toshiba MMY-MAP1004HT5P Service Manual page 144

Hide thumbs Also See for MMY-MAP1004HT5P:
Table of Contents

Advertisement

A
Operation start
Press the push-switch SW04 on the interface P.C.
board of the header unit for 2 seconds or more. The
operation starts.
Check that 7-segment display [B] shows [ CC] for
cooling and [ HH] for heating.
Confirmation of check results (1)
Check that No. of misconnected indoor units is
displayed on 7-segment display [B] after 15 minutes.
(If there is no misconnection, [00P] is displayed.)
Confirmation of check results (2)
Press the push-switch SW05 on the interface P.C. board
of the header unit for 2 seconds or more. The indoor
address in which error is being detected is displayed on
7-segment display [B]. If there are multiple indoor
address in which error is being detected, they are
successively exchanged and displayed.
(When SW05 is turned on again, the display returns to
display of No. of units.)
After check, return the rotary switches
SW01/SW02/SW03 on the interface P.C. board of the
header unit to [1/1/1].
(7-segment display)
[A]
[B]
Cooling
[ C
]
[ CC ]
Heating
[ H
]
[ HH ]
(7-segment display)
[A]
[B]
[
]
[ # # P]
No. of misconnected
C or H
indoor units
(7-segment display)
[A]
[B]
[
]
[
# # ]
Address display
C or H
of misconnected
indoor unit
(7-segment display)
[A]
[B]
[U1]
[
]
7-segment display [A]
7-segment display [B]
SW04
SW05
SW01
SW02
<Rotary switches>
– 143 –
Operation
This check operation
requires 15 minutes
even if there is no
misconnection or there
is any misconnection.
SW03

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents