Node Report - Emerson Bettis XTE3000 Installation, Operation And Maintenance Manual

Profibus dpv2 slave redundancy module
Table of Contents

Advertisement

Installation, Operation and Maintenance Manual
MDE 256 Rev. 1
Configuration procedure:
View procedure:
9.2

Node Report

The following procedure allows seeing the most significant info relevant to the bus data transmission
of the actual Primary Slave interface card and the actual Backup Slave interface card.
The following indication are reported:
CARD REPORT
STATUS 0
Table 4.
b7
-
-
X
Local Operator Interface Commissioning
Move the local selector to OFF and then press simultaneously OPEN and STOP. Select the
language and then enter the password according to the instructions "entering the set-up
mode". When the message of display is "SET-UP MODE OK?" press YES. Press YES to select
"ACTUATOR SET-UP" menu, press NO to scroll the list of available routines and then press
YES to select BUS CONTROL.
Press YES if the condition linked to DIN 1 is correct, or press NO to change, then press YES.
Repeat the previous step for DIN 2, DIN 3 - DIN 6.
Press YES if the configured value of the node address (NODE) is correct (from 1 to 126),
or press NO to change, then press YES.
Press YES if the configured value of the node address (NODE-B) is correct (from 1 to 126),
or press NO to change, then press YES.
Press YES if the configured status of termination 1 (TERMIN 1) is correct (ON / OFF),
or press NO to change, then press YES.
Press YES if the configured status of termination 2 (TERMIN 2) is correct (ON / OFF),
or press NO to change, then press YES.
Move the local selector to OFF and then press simultaneously OPEN and STOP. Select the
language and then enter the password according to the instructions "entering the view
mode". When the message of display is "VIEW MODE OK?" press YES. Press YES to select
"ACTUATOR SET-UP" menu, press NO to scroll the list of available routines and then press
YES to select BUS CONTROL.
Press YES to scroll the list of BUS CONTROL parameters.
By this routine, it is possible to show the 64 characters identification string relevant to the
actual Primary Slave interface card.
These informations are from the actual Primary Slave PROFIBUS card.
b6
b5
b4
b3
-
-
-
-
-
X
X
-
X
-
-
-
Section 9: Local Operator Interface Commissioning
b2
b1
b0
Status of the Actual Slave
-
X
-
1 = Active and RUN
Status of the Internal Data Area
0 0 = Data Area empty
-
-
-
0 1 = Data Area being read from base card
1 0 = Data Area completely transferred
Status of the Actual Slave
0 0 = Undefined
-
-
-
0 1 = Backup
1 0 = Primary
1 1 = Not permitted
March 2022
Description
25