14 - All venting pipe passing through floors, walls, and
ceilings must be installed with the listed clearance
to combustible materials and be fire stopped
according to local codes. In absence of local codes,
refer to NFGC (Z223.1).
15 - No portion of the venting system can extend into,
or pass through any circulation air duct or plenum.
16 - Vent connectors serving Category I appliances shall
not be connected to any portion of mechanical draft
systems operating under positive pressure such as
Category III or IV venting systems
17 - If vent connectors are combined prior to entering
the common vent, the maximum common vent
capacity listed in the common venting tables must
be reduced by 10%, the equivalent of one 90° elbow
(0.90 x maximum common vent capacity).
Capacity of Type B Double-Wall Vents with Type B Double-Wall Connectors
Height
Lateral
H
L
(feet)
(feet)
0
2
6
4
6
0
2
8
5
8
0
2
10
5
10
0
2
15
5
10
15
0
2
5
20
10
15
20
0
2
5
30
10
15
20
30
NOTE - Single appliance venting configurations with zero lateral lengths are assumed to have no elbows in the vent system. For
all other vent configurations, the vent system is assumed to have two 90° elbows. For each additional 90° elbow or equivalent (for
example two 45° elbows equal one 90° elbow) beyond two, the maximum capacity listed in the venting table should be reduced by
10 percent (0.90 x maximum listed capacity).
Serving a Single Category I Appliance
Vent and Connector Diameter - D (inches)
3 inch
Appliance Input Rating in Thousands of Btu Per Hour
Min
Max
Min
0
78
13
51
21
49
25
46
0
84
12
57
23
53
28
49
0
88
12
61
23
57
30
51
0
94
11
69
22
65
29
59
35
53
0
97
10
75
21
71
28
64
34
58
48
52
0
100
9
81
21
77
27
70
33
64
56
58
NA
NA
18 - The common vent diameter must always be at least
as large as the largest vent connector diameter.
19 - In no case, shall the vent connector be sized more
than two consecutive table size diameters over the
size of the draft hood outlet or flue collar outlet.
20 - Do not install a manual damper, barometric draft
regulator or flue restrictor between the furnace and
the chimney.
21 - When connecting this appliance to an existing
dedicated or common venting system, you must
inspect the venting system's general condition
and look for signs of corrosion. The existing vent
pipe size must conform to these instructions and
the provided venting tables. If the existing venting
system does not meet these requirements, it must
be reized.
TABLE 3
4 inch
Max
Min
0
152
18
97
27
30
94
39
36
91
47
0
165
16
109
25
32
103
42
39
98
51
0
175
17
118
23
32
113
41
41
104
54
0
191
15
136
20
30
130
39
40
121
51
48
112
61
0
202
14
149
18
29
143
38
38
133
50
46
124
59
55
116
69
0
213
13
166
14
28
160
36
37
150
48
44
141
57
53
132
66
73
113
88
Page 16
5 inch
Max
Min
0
251
157
32
153
50
149
59
0
276
178
28
171
53
164
64
0
295
194
26
187
52
176
67
0
327
226
22
219
49
206
64
195
76
0
349
250
20
242
47
229
62
217
73
206
84
0
374
283
18
275
45
262
59
249
70
237
80
214
104
6 inch
Max
0
375
232
227
223
0
415
263
255
247
0
447
289
280
267
0
502
339
330
315
301
0
540
377
367
351
337
322
0
587
432
421
405
389
374
346