3-3. System in which BAC-HD150 is connected to the expansion controller

The figure below only shows the transmission line connections. Power supply lines are omitted.
Building Management System
192.168.1.100
HUB
HUB
LAN1
BM ADAPTER
Model: BAC-HD150
®
BACnet
192.168.1.254 (LAN1)
192.168.200.212 (LAN2)
(LAN)
Centralized controller
Model:
AG-150A
192.168.200.201
• Refer to the PAC-YG50ECA Installation/Instructions Manual for how to set the IP address.
• The same M-NET address cannot be used twice in the same M-NET system that connects to the same PAC-YG50ECA.
NOTES
* The BAC-HD150 and the type of controllers that connect to the expansion controller via the LAN (e.g., AG-150A) each have a DB No.
This 2-digit number is indicated on the package box and the controller. ([DB No.:**])
Controllers with different DB No. cannot be connected to each other. Be sure to check the DB No. of each controller to be connected.
Connection of two or more controllers that have different DB No. requires a controller software version update. Consult your dealer for
how to update the software.
Label contents
* Use a switching HUB.
* Provide "one-point grounding" for the M-NET transmission line (centralized control system) by grounding the shield of each
expansion controller.
Ground the indoor-outdoor transmission line in each outdoor unit refrigerant system.
* Set the centralized control switch (SW2-1) on the outdoor units on the M-NET line to ON.
(Refer to the outdoor unit Installation Manual for the details of the dipswitch settings.)
Mitsubishi Electric air conditioning system
LAN2
LAN
HUB
Expansion controller
LAN
Model:
PAC-YG50ECA
192.168.200.213
[000]
LAN
LAN
Expansion controller
Model:
PAC-YG50ECA
192.168.200.214
[000]
LAN
Expansion controller
Model:
PAC-YG50ECA
192.168.200.215
[000]
M-NET
Outdoor unit
[051]
Group 1-1
TB7 TB3
M-NET
[001]
[002]
ME
[101]
M-NET
R2
BC controller
Outdoor unit
[056]
[057]
TB7 TB3
M-NET
Outdoor unit
Group 2-1
[051]
TB7 TB3
M-NET
[001]
[002]
ME
[101]
M-NET
Outdoor unit
Group 3-1
[051]
TB7 TB3
M-NET
[001]
[002]
ME
[101]
DB No. appears here.
- 10 -
Indoor unit
Local remote
controller
LAN
M-NET
transmission line
Figures in
indicate IP address.
Figures in [ ] indicate M-NET address.
Group 1-2
[003]
[004]
[005]
ME
[103]
Group 1-3
[006]
[007]
[008]
[009]
ME
[106]
LOSSNAY
Group 2-2
[003]
[004]
ME
[103]
Group 3-2
LOSSNAY
[003]
[004]
ME
[103]
LOSSNAY
[010]
[005]
[005]