Hitachi RAS-08HT Installation Instructions Manual page 10

Split inverter type room air conditioner

Advertisement

2
Preparing the pipes
The pressure of refrigerant R410A is higher than
that of R22, and thus the thickness of copper
pipes must comply with that shown in the right
table. The copper pipe of 0.7 mm thickness
available on the market must not be used.
Cutting and flaring operation of copper tubes
Use pipe cutter to cut the copper pipe
perpendicularly.
Pipe cutter
Copper pipe
Tighten the pipe
cutter to cut the
copper pipe
When deburring the copper pipe, point
down to the pipe to avoid copper chips
coming in the pipe.
Ensure that the
inside of copper
tube has no
scratches.
Perform the pipe flaring.
Check the pipe flares. Poor flaring
will cause leakage when they are
jointed.
Example of poor flaring:
Scratches
Incomplete deburring
Copper chips scratch the inside
3
Precautions for refrigerant piping
Pipe
Burr
Deburring tool
Rubber band
Cap and
plastic
Without
touching
Ground
the ground
4
Jointing the pipes
Remove the
flare nut.
Align and
tighten the
pipe end with
[ Screw all the way
down with hand] ]
hand.
Thickness of copper pipes for general refrigerant pipes.
Rotate to right
to feed the
knife.
Handle
Deburring tool
Press
die
Under flaring
Copper chips and copper
powder come in the pipe
Sealed
Indoor
Outdoor
Outdoor
Sealed
Indoor
Foreign
matters and
Ground
water enters
Notice: Before joining the pipes, apply some refrigerating oil at the flare opening
to ensure no leakage from the joint.
After tightening with a wrench, slightly screw
backward and then tighten it using the torque
wrench.
10
Nominal outer
Standard outer
diameter (inch)
diameter (mm)
1/4
6.35
Ø
Ø
3/8
9.52
Ø
Ø
1/2
12.7
Ø
Ø
5/8
15.88
Ø
Ø
Before flaming the pipe with a flaming tool, do not forget
to fit a flare nut.
Tighten the pipe
cutter to cut the
copper pipe
Flare nut
Copper pipe
【Size of overhang
(Strictly observe the size of overhang to
of copper pipe】
avoid leakage.)
Outer diameter(Ø) Tool for R410A
6.35(1/4")
0~0.5
9.53(3/8")
0~0.5
12.7(1/2")
0~0.5
15.88(5/8")
0~0.5
Copper pipe
Over flaring
Cap and plastic bag
Tying with a rubber
band
Foreign matters and
water enters
Outdoor
Indoor
Wall
Cap and plastic
Tying with a
rubber band
[
Tightening torque
Liquid diameter
Do not tighten all
the way in a
Gas diameter
sudden, but screw
Gas diameter
slowly and tight it
Gas diameter
Thickness of copper
tube (mm)
0.8
0.8
0.8
1.0
Flaring tool
Screw gripper
A (mm)
Tool for R22
1.0
1.0
1.0
1.0
Cracking
Rain enters
the pipe
Sand enters the
pipe
]
Outer diameter
Torque (kgf-cm)
(Ø)
6.35(1/4")
140~190
9.53(3/8")
350~450
12.7(1/2")
450~550
15.88(5/8")
500~600