York MILLENNIUM YCAL0043SC Manual page 34

Air-cooled liquid chillers hermetic scroll
Table of Contents

Advertisement

Installation
DIMENSIONS (ENGLISH)
YCAL0073SC - YCAL0107SC
LD04403
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated
performance, reliable operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated
below, resulting in unpredictable airflow patterns and possible diminished performance. YORK's unit controls will optimize
operation without nuisance high-pressure safety cutouts; however, the system designer must consider potential perfor-
mance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators. Recommended
minimum clearances: Side to wall – 6'; rear to wall – 6'; control panel to end wall – 4'; top – no obstructions allowed;
distance between adjacent units – 10'. No more than one adjacent wall may be higher than the unit.