IBC HC 15-95 Installation And Operating Instructions Manual page 16

Table of Contents

Advertisement

WARNING
It is extremely important to
maintain at least the minimum
separation of exhaust vent
termination from boiler intake
air as illustrated in figures
5, 8 and 13. Failure to do so
can result in a dangerous
situation where exhaust
gasses are re-ingested with
combustion air. Damage to
the boiler can result from
a failure to maintain these
separations. Improper
installation will void the
warranty.
WARNING
In areas of high snowfall,
Users must be advised to
check side wall vent and
air intake terminations on
a regular basis to ensure
blockage does not occur.
1-10
HC SERIES BOILERS HC 13-50, HC 15-95, HC 15-96, HC 20-125, HC 33-160
Use a 45° elbow on the exhaust termination to launch the plume up and off
the sidewall, for protection of wall.
Bird screen of 1/4" stainless steel or plastic mesh eg. (IPEX System 636 drain
grate for CPVC systems) is useful to guard against foreign objects.
Figure 8: Sidewall vent termination - piping configuration
DIRECT VENT SIDE WALL TERMINATION KITS
The following Side Wall Termination Kits are approved for use with the HC series
boilers and are subject to the following restrictions.
may not allow this type of side wall termination due to close proximity to the
neighboring properties. See Figures 9a, 9b and 10 on page 1-11.
The installation instructions, clearances and wall thickness requirements of the
approved vent termination manufactures must be followed.
Approved Side Wall Termination Kits are listed as follows: (Alternate vent
termination kits must be submitted to IBC for approval prior to installation.)
Ipex - #196984 – 2" PVC low profile termination kit (see Figure 10).
Ipex - #196985 – 3" PVC low profile termination kit (see Figure 10).
NOTE:
INSTALLATION AND OPERATION INSTRUCTIONS
Some jurisdictions