Controller operation-Function settings

Night setback

Function description
This control starts heating operation when the control object group is stopped and the room temperature
drops below the preset lower limit temperature. Also, this control starts cooling operation when
the control object group is stopped and the room temperature rises above the preset upper limit
temperature.
The Night setback function is not available if the operation and the temperature setting are performed
from the remote controller.
If the room temperature is measured by the air-conditioner's suction temperature sensor, the accurate
temperature may not be obtained when the air-conditioner is inactive or when the air is not clean. In
this case, switch the sensor to a remote sensor (PAC-SE40TSA/PAC-SE41TS-E) or a remote control
sensor.
Button operation
1
Main
Restriction
Energy saving
Night setback
Filter information
Error information
Main display:
Cursor
F1
2
Night setback Yes
Temp. range
Start
Stop
Setting display:
F1
42
Main menu
Page
F2
F3
F4
Night setback
12
- 28
23:00
5:00
F2
F3
F4
Select "Night setback" from the Main menu (refer
to page 20), and press the SELECT button.
The current settings will appear.
Press the SELECT button to go to the setting
screen.