Shielding The Connections; Motor Rotation - Riello RS 1000/EV C01 Installation, Use And Maintenance Instructions

Forced draught gas burner
Table of Contents

Advertisement

5.12.2 Shielding the connections

For the burner to operate correctly, where re-
quired, it is necessary to shield the connections.
WARNING
To shield the motor connection, proceed as follows:
➤ to access the motor casing, loosen the four screws
1)(Fig. 24) and remove the cover 2);
➤ remove the shielded coupling 3) screwed to the motor cas-
ing.
To make the correct shielding, it is important to
bear in mind the necessary length of the connec-
tions inside the motor casing.
CAUTION
➤ Shield the cable 4) running from the VSD (inverter), as
shown in Fig. 25 and using the coupling 6);
➤ install the cable 4) with its relative coupling on the motor cas-
ing, fixing it carefully in place with the ring nut 5)(Fig. 24).
➤ Carry out the motor connection as shown in the wiring dia-
grams.
➤ Fix the grommets/cable terminals of the connections
securely and tidily to the terminal board of the motor.
➤ Make a final visual check, then close the motor casing by
tightening the 4 screws 1)(Fig. 24).

5.12.3 Motor rotation

As the burner is not fitted with a phase sequence checking de-
vice, the motor rotation may be incorrect.
As soon as the burner starts up, go in front of the
fan motor cooling fan and check it is rotating anti-
clockwise (Fig. 26).
WARNING
If this is not the case:
➤ turn the burner switch to position "0" (OFF) and wait for the
control box to carry out the switch-off phase;
➤ disconnect the power supply to the main panel;
➤ invert the phases on the three-phase power supply.
This operation must be carried out with the electri-
cal supply disconnected.
DANGER
20062132
Installation
20082670
4
24
GB
6
D8177
20079199
Fig. 24
Fig. 25
Fig. 26

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rs 1200/ev c012006212820062129

Table of Contents