Installation Clearance Requirements - CanadianSolar CSI-75K-T40001-E Quick Installation Manual

Pv inverter
Hide thumbs Also See for CSI-75K-T40001-E:
Table of Contents

Advertisement

Vertical
Backward
Forward
Upside down
≥ 10
FIG 3-2 Installation angle

3.4 Installation Clearance Requirements

Reserve enough clearance around the inverter to ensure sufficient space for heat dissipation. ( 3-3 The fans are
1)
maintained on the left side of the inverter, and a larger clearance is required.)
In case the distance is less than 800mm, move the inverter from the mounting-bracket or wall before maintaining fans
In case of multiple inverters, reserve specific clearance between the inverters. 3-4
2)
≥ 600mm
≥ 500mm
FIG 3-3 Single installation space
800mm
800mm
400mm
FIG 3-4 Multiple installation space
3 / 18