Download Print this page

Mitsubishi Electric PUZ-ZM100VKA.UK Service Manual page 59

Advertisement

10-6. HOW TO CHECK THE PARTS
PUZ-ZM100VKA.UK
PUZ-ZM100VKAR1.UK
PUZ-ZM100YKA.UK
PUZ-ZM100YKAR1.UK
Parts name
Disconnect the connector then measure the resistance with a tester.
Thermistor (TH3)
(At the ambient temperature 10 to 30°C)
<Liquid>
Thermistor (TH4)
<Discharge>
Thermistor (TH6)
TH4, TH33
<2-phase pipe>
Thermistor (TH7)
<Ambient>
1
Thermistor (TH8)*
<Heat sink>
Thermistor (TH33)
<Comp. Surface>
Fan motor(MF1,MF2)
Refer to the next page.
Solenoid valve coil
Measure the resistance between the terminals with a tester.
(At the ambient temperature 20°C)
<4-way valve>
(21S4)
Motor for compressor
Measure the resistance between the terminals with a tester.
(Winding temperature 20°C)
U
(MC)
V
W
Linear expansion valve
Disconnect the connector then measure the resistance with a tester.
2
(LEV-A/LEV-B/LEV-C
*
)
(Winding temperature 20°C)
Gray
M
1
Orange
2
Red
3
Yellow
4
Black
5
1
*
ZM100–140Y
2
*
LEV-C is for ZM140 model only.
OCH654D
PUZ-ZM125VKA.UK
PUZ-ZM125VKAR1.UK
PUZ-ZM125VKAR2.UK
PUZ-ZM125YKA.UK
PUZ-ZM125YKAR1.UK
PUZ-ZM125YKAR2.UK
Normal
160 to 410 k"
TH3
TH6
4.3 to 9.6 k"
TH7
TH8
39 to 105 k"
Refer to "5-2. COMPRESSOR TECHNICAL DATA".
Gray - Black
Gray - Red
PUZ-ZM140VKA.UK
PUZ-ZM140VKAR1.UK
PUZ-ZM140VKAR2.UK
PUZ-ZM140YKA.UK
PUZ-ZM140YKAR1.UK
PUZ-ZM140YKAR2.UK
Checkpoints
Abnormal
Open or short
Normal
ZM100–140
1435 ± 150 "
Normal
Normal
Gray - Yellow
46 ± 3 "
59
Abnormal
Open or short
Abnormal
Open or short
Abnormal
Gray - Orange
Open or short

Advertisement

loading

This manual is also suitable for:

Puz-zm125vkaPuz-zm140vkaPuz-zm100ykaPuz-zm125ykaPuz-zm140ykaPuz-zm100vka ... Show all