Advertisement
Installation of the ICM325HN shall be performed by trained technicians only. Adhere to all local and national electric codes.
Disconnect all power to the system before making any connections.
With probe temperatures above 100°F, the control applies full voltage to the motor. The green light is illuminated (full speed LED).
With probe temperatures between 70°F and 100°F, the motor speed is proportional to the probe temperature. The yellow light is illuminated (variable speed LED).
When the motor starts at temperatures between 70°F and 100°F, it will hard start for the length of time dictated by the hard start dial setting. After the hard start time has elapsed, the motor speed is controlled by the probe temperature.
As the temperature being sensed decreases, the output voltage decreases. The output voltage may decrease to the determined cutout speed dictated by the cutout speed dial. Upon reaching the cutout speed setting, the output voltage goes to zero volts.
System restart will occur when the temperature exceeds 70°F.
With probe temperatures below 70°F, the motor remains off. The green light and the yellow light are off.
Heat pump bypass mode runs the fan at full speed when the system is operating in heat mode. This moves as much air as possible across the condenser coil.
If the heat pump select jumper is in the N.O. position, and 24 VAC is applied to the HP terminals, the motor will be brought to full speed.
If the heat pump select jumper is in the N.C. position, and 24 VAC is not present at the HP terminals, the motor will be brought to full speed.
A separate relay is not needed.
The cutout speed dial adjusts the motor voltage range. Set the cutout voltage dial according to the type of motor you have.
Set the cutout speed dial to the middle of the sleeve bearing range. In this range, the motor can run down approximately 40-50% of the full line voltage, which allows sufficient RPMs for cooling and lubrication.
With sleeve bearing motors, it is important not to adjust outside the sleeve bearing range or bearing failure may result.
Set the cutout speed dial to the MIN position in the ball bearing range. This position offers the greatest range of speed control. At the MIN setting the motor can run down to approximately 20-30% of the full line voltage.
Note: After starting at the recommended settings for either sleeve or ball bearing motors, you can fine tune the cutout speed to achieve the desired results.
During the Hard Start mode, full voltage is applied to the motor during startup to overcome windmilling and to lubricate the bearings.
The position of the hard start dial determines the time period of the hard start mode.
The dial can be adjusted between 0.1 second and approximately 5 seconds.
Set the hard start dial according to the type of motor you have. If you have a ball bearing motor, set the hard start dial to the MIN position. If you have a sleeve bearing motor, set the hard start dial to the middle of the sleeve bearing range.
After you begin at the recommended setting, you can fine tune the hard start time within the recommended range for the type of motor you have.
It is recommended that you use the minimum possible hard start time to avoid blowing too much cold air over the condenser.
Hard Start mode is activated when 24 VAC is applied (or disconnected and re-applied) or the probe temperature increases to above 70°F. The hard start mode applies full voltage to the motor for the set time period. Afterwards, the motor speed is dictated by the temperature sensor(s).
Symptom | Problem | |||
Unit fails to start | The sensor may not be connected or it is defective. With the probe disconnected, use an ohmmeter to measure the resistance between the probe wires. It should match the chart in "Temperature vs. Probe Resistance" (see below). If you read an OPEN or SHORT, replace the sensor. | |||
Fuse and/or circuit blows | The unit has been miswired and may be permanently damaged. | |||
The fan cycles from full ON to full OFF with little or no modulation | Turn OFF the control circuit power (24 VAC). Re-apply 24 VAC power and confirm hard start operation. Reduce the hard start period to the minimum setting required to accelerate the fan. Excessive hard starting causes large pressure drops by running too much cold air over the condenser. Should the cycling persist, move the probe up several bends into the condenser to increase the sensitivity to condensing temperature. Adjust probe location. Fine tune cutout adjustment. | |||
The fan does not come on at all | Using an AC voltmeter, measure the voltage between the 24 VAC terminals. It should read approximately 24 volts. Measure the line voltage between LINE 1 and LINE 2 to confirm that the line voltage is present. Remove the thermistor probe from the terminal block and measure its resistance at ambient temperature. Compare your reading at the appropriate temperature in "Temperature vs. Probe Resistance" to see if the actual resistance approximates the listed value. Next, hold the probe in your hand and confirm that the resistance decreases. Place a temporary jumper across the S2 or S3 terminals. Fan should run at full speed. If it does, recheck probe connection and verify probe is operating correctly. | |||
The high pressure switch trips off | Move the probe further into the condenser where the temperature is higher. This will produce a higher fan RPM and will decrease the head pressure. Fine adjust the cutout and hard start settings. | |||
Green and yellow LEDs alternate | Using an AC voltage meter, measure the voltage between the 24 VAC terminals. Also verify you have the voltage between Line 1 and LINE 2 terminals. |
When a sensor is mounted into the condenser, the control responds more rapidly to changes in head pressure than when it is mounted on the liquid line. This is especially true for high efficiency condensers.
When the sensor is mounted on the liquid line, the control responds more slowly and the results can be a fan that cycles on and off.
Whenever possible, it is preferable to mount the sensor in the upper 1/3 of the condenser instead of mounting it on the liquid line (see illustration below). A spot on the condenser that is 100F when the pressures are correct is ideal.
°C | °F | Resistance (KΩ) |
0° | 32° | 32.7 |
5° | 41° | 25.4 |
10° | 50° | 19.9 |
15° | 59° | 15.7 |
20° | 68° | 12.5 |
25° | 77° | 10.0 |
30° | 86° | 8.1 |
35° | 95° | 6.5 |
40° | 104° | 5.3 |
45° | 113° | 4.4 |
50° | 122° | 3.6 |
For more information on our complete range of American-made products – plus wiring diagrams, troubleshooting tips and more, visit us at www.icmcontrols.com
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.
Download ICM Controls ICM325HN - Head Pressure Control Manual
Advertisement
Thank you! Your question has been received!
Need Assistance?
Do you have a question about the ICM325HN that isn't answered in the manual? Leave your question here.