COMPONENT IDENTIFICATION
Status Indicator LEDs
PC Configurator Jack
Connector for
MECHATROLINK
Communication
Station Address Setting Rotary SW
■ STATUS INDICATOR LED
ID
COLOR
FUNCTION
PWR
Green
Turns on when the internal power is sup-
plied normally.
ERR
Red
Turns on at MECHATROLINK-III com-
munication error
CON
Green
Turns on at MECHATROLINK-III con-
nection is established
LNK1
Green
Turns on at MECHATROLINK-III LNK1
is established
LNK2
Green
Turns on at MECHATROLINK-III LNK2
is established
■ DISCRETE OUTPUT STATUS INDICATOR LED
LED green indicators shows the output signal status.
ON : LED ON
OFF : LED OFF
PWR
CON
LNK2
CNFG.
X0
X1
X2
X3
X4
X5
X6
X7
ERR
LNK1
SA1 X10
SA2 X1
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
Discrete Output Status Indicator LEDs
X8
X9
XA
XB
XC
XD
XE
XF
X10 X11 X12 X13 X14 X15 X16 X17
X18
X19
X1A
Output Connector
■ STATION ADDRESS
Station Address is selected between 03H and EFH in hexa-
decimal.
The SA1 switch determines the MSD, while the SA2 switch
does the LSD of the address.
(Factory setting: 03H)
R7I4DML3-DC32A
X1B
X1C
X1D
X1E
X1F
Terminals for
Power Supply &
Sencor Excitation
Station Address Setting SA1 (MSD) (x10)
Station Address Setting SA2 (LSD) (x1)