(9) Checking the indoor electrical equipment
(a) Indoor PCB check procedure
Is there voltage between terminal
blocks ① and ② ? (AC 220/230/240
V)
YES
Is the fuse burnt out? (3.15 A)
YES
Is the voltage between terminal
blocks ② and ③ oscillating between
DC 0 and 20V?
YES
Indoor electrical components
are normal.
(b) Indoor unit fan motor check procedure
1) Indoor PCB output check
DC several V
(4~6 V)
CNU
2) Fan motor resistance check
Measuring point
①  −  ③
④  −  ③
NO
Inspect power source
for outdoor unit.
NO
Replace fuse.
NO
Replace indoor PCB.
(–)
GND
DC15V
FM
I
Resistance when normal
k
Defrosting is performed for 10 minutes at approx. 35 (model SRK35:45) minutes.
Defrosting is performed for 10 minutes at approx. 35 (model SRK35:45) minutes.
DC 308~336V
Indoor PCB
56
-
-
'13 • SRK-T-140
① ④
Measuring
Resistance when
point
normal
①  −  ③
④  −  ③
⑤  −  ③
⑥  −  ③