Nortel CTR 2800 Installation Manual page 41

Outdoor microwave transceiver
Table of Contents

Advertisement

Ground connections to outdoor equipment
The grounding lug is supplied with all current releases of outdoor brackets. In
addition, a 6 AWG braided ground wire connected to the common bonding
network is required to complete the ground connection for all microwave
products.
Note: There is no grounding lug supplied with previously-released
microwave products. To retrofit these installations, order one retrofit kit
for each sector and use the following procedures.
Retrofit procedure for grounding the base station equipment
(BTR and RPE)
You will need an NTVG15BA BTR and RPE grounding retrofit kit for every
base station sector to be retrofitted, containing the following parts:
Item
Qty
Vendor part no.
1
2
LCA6-38
2
1
LCA6-14
3
2
W-2064
4
2
W-2069
Use the following method to install the kit on the BTR, referring to Figure 2-4:
1
2
3
Use the following method to install the kit on the RPE, referring to Figure 2-4:
1
2
3
4
5
6
6 AWG, 3/8" compression terminal (Panduit) for BTR
6 AWG, 1/4" compression terminal (Panduit) for RPE
1/4" Stainless steel internal tooth lock washer (Spaenaur) for RPE
3/8" Stainless steel internal tooth lock washer (Spaenaur) for BTR
Remove the 3/8" mounting bolt, two flat washers and the mounting
washer from the BTR. Discard one flat washer and the locking washer.
Crimp the 3/8 terminal (A0297956) onto the grounding wire.
Install the existing bolt, flat washer, new internal tooth washer, and the
complete ground cable as shown in Figure 2-4
Remove the 1/4" mounting bolt and split lock washer as shown in
Figure 2-4
.
Crimp the 1/4 terminal (A0315080) onto the grounding wire.
Install the ¼" original mounting bolt and a stainless steel internal tooth
washer.
Repeatedly tighten and loosen the fastener assembly, rotating the
internal tooth lock washer, until the powder coating is scraped off and
the bare metal is exposed. Repeat this procedure if required.
Discard the internal tooth washer used to remove the powder coating.
Using new stainless steel internal tooth washers, assemble the complete
ground cable connection, as per Figure 2-4.
Grounding and Surge Protection 2-7
Description
.
Reunion CTR 28 GHz Installation Guide
CPC no.
A0297956
A0315080
TBD
TBD

Advertisement

Table of Contents
loading

This manual is also suitable for:

28-01p128-01p228-07p

Table of Contents