Nortel CTR 2800 Installation Manual page 35

Outdoor microwave transceiver
Table of Contents

Advertisement

Grounding and Surge Protection
2
Grounding/Lightning Protection
Scope
This chapter presents guidelines for the grounding and electrical protection of
Reunion equipment in typical buildings, assuming
1. indoor equipment is installed in an appropriate equipment room and
2. outdoor equipment is installed on rooftops using a pole mount.
Further, Nortel Networks assumes building electrical systems comply with
the appropriate national and local regulations.
Grounding Methods/Indoor Equipment
Components of a communications system can be grounded together using an
isolated bonding network (IBN). The IBN can be configured in several different
ways:
1. Mesh
2. Mesh – IBN with bonding mat
3. Star or sparse-mesh
In turn, the IBN is bonded at a single point to the Common Bonding Network
(CBN) that forms the principal bonding network in a building. Figure 2-1
shows a typical installation:
Reunion CTR 28 GHz Installation Guide
2-1

Advertisement