Mitsubishi Electric FR-E8TR Instruction Manual page 40

Rs-485 2 port terminal block
Table of Contents

Advertisement

Pr.
728
Device instance number (Upper 3 digits)
N052
729
Device instance number (Lower 4 digits)
N053
*1
When Pr.73 = "6", the operation is the same as the one when the setting is "1". When Pr.73 = "16", the operation is the same as the one
when the setting is "11".
*2
When "1" (MODBUS RTU protocol) is set in Pr.549, the setting range within parentheses is applied.
*3
When Pr.549 = "2" (BACnet MS/TP protocol), the setting range within parentheses is applied.
*4
Initial values of parameters differ depending on the parameter initial value group (1 or 2).
40
OPERATION VIA COMMUNICATION FROM RS-485 TERMINALS
Initial
Name
value
0
0
Setting range
0 to 419
Device identifier
(0 to 418)
When the figure obtained by combining the
Pr.728 and Pr.729 settings is not within "0 to
4194302", the setting is out of range.
When Pr.728 = "419", the setting range of Pr.729
0 to 9999
is "0 to 4302".
(0 to 4302)
When Pr.729 = "4303" or more, the setting range
of Pr.728 is "0 to 418".