Pr.
121
Number of PU communication retries
N025
122
PU communication check time interval
N026
123
PU communication waiting time setting
N027
124
PU communication CR/LF selection
N028
343
Communication error count
N080
390
% setting reference frequency
N054
549
Protocol selection
N000
38
OPERATION VIA COMMUNICATION FROM RS-485 TERMINALS
Initial
Name
value
1
0
9999
1
0
60 Hz /
50 Hz
0
Setting range
Set the permissible number of retries for
unsuccessful data reception. If the number of
0 to 10
consecutive errors exceeds the permissible
value, the inverter output is shut off.
The inverter output will not be shut off even
9999
when a communication error occurs.
RS-485 communication is enabled. However, the
inverter output is shut off if the operation mode is
0
changed to the one for the selected command
interface.
Set the interval of the communication check
(signal loss detection) time.
0.1 to 999.8 s
If a no-communication state persists for longer
than the permissible time, the inverter output will
be shut off.
9999
No communication check (signal loss detection)
Set the waiting time between data transmission
0 to 150 ms
to the inverter and the response.
Set with communication data.
9999
Waiting time: setting data × 10 ms
0
Without CR/LF
1
With CR
2
With CR/LF
Displays the communication error count during
(0 to 999)
MODBUS RTU communication. (Read-only)
1 to 590 Hz
Set a reference frequency of the set frequency.
*4
0
Mitsubishi inverter protocol (computer link)
1
MODBUS RTU protocol
2
BACnet MS / TP protocol
Description