Download Print this page

ABB Cylon MATRIX-2 Installation And Wiring page 2

Hide thumbs Also See for Cylon MATRIX-2:

Advertisement

Numbers
39 ... 42
Indicator LEDs
Note: During typical operation, the Red LED
should be on, the Green LED should be
blinking and the Yellow LED should be off.
Red LED
(Power)
Green LED
(Status)
Yellow LED
(FLX)
For further information on installing and configuring the MATRIX-2 device
see the MATRIX-2 Series Installation manual:
https://share.library.abb.com/api/v4?cid=Root&q=MAN0155
©ABB 2023 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
Terminal
Description
93, 94
24 V AC Power
Important: The common power
connection (terminal
connected to Earth. ABB Cylon
recommend that this is done at
the 24 V AC transformer.
95, 96
RS-485 Port 1 (isolated) screw terminal
The bus Terminator Switch is located
beside the port. If the switch is
towards the
icon, then termination
is
and if the switch is towards the
in
icon then termination is out.
RS-485 Port 2 (non-isolated) screw
terminal
The bus Terminator Switch is located
beside the port. If the switch is
towards the
icon, then termination
is
and if the switch is towards the
in
icon then termination is out.
Note: There is no support for a Sensor
on the MATRIX-2, so terminal
is
42
Not
Connected.
Off
On
Slow Blink
Power is
Power is
___ Unit Rebooting ___
off
on
Unit is not
Unit is
running
running
___ Not Used ___
) must be
93
Restart the device leaving all ethernet settings and passwords
intact:
while the controller is
The red indicator LED will remain on.
Fast blink
The Green indicator LED will stay off until reboot in complete.
The Green indicator LED will begin to flash when reboot is
done.
The Yellow indicator LED will be off unless there is a problem
Ethernet Ports
Service Port (Micro USB)
USB ports
Reserved for firmware upgrade.
Push buttons
Reset Ethernet settings (IP address) only :
running
while the controller is
, press
for 1 second.
On release, LED
will light up.
L2
All ethernet settings will be returned to
factory defaults 192.168.1.251/24.
Groups and Users (passwords) will remain
intact
Reset everything to factory defaults :
running
while the controller is
, press and
hold
.
SW1
After 3 seconds LED
will light up,
L2
continue to hold
for at least 10
SW1
seconds.
Release
. All ethernet settings will be
SW1
returned to factory defaults
192.168.1.251/24.
Groups and Users (passwords) will be reset
to factory defaults.
running
, press
for 1 second.
SW2
LED L1 / LED L2
Red L2 lights up when reset is triggered.
SW1
2

Advertisement

loading