VIPA HMI
System setting (Control
Panel)
Set MPI parameters
HB160 | TP | 62K-JIDR | en | 20-20
As many components of the Control Panel conform with the system control of Windows
most of the description is not necessary. The description of the control panel components
relevant for operating the Touch Panel can be found in the following:
n
Set display
Via 'Start è Settings è Control Panel è Display' the dialog windows for the display
properties opens. Here you can change the settings for the monitor options.
n
Calibrate touch screen
If the touch screen does not always react to a double click or not precisely recognize
the position of an entry, you can call the dialog Stylus via 'Start è Settings
è Control Panel'. In the register Double-Tap you can use the grid pattern to preset a
double click velocity and test this on the symbol below. Click [OK] to accept the value.
The calibration of the touch screens is completed via the register Calibration by fol-
lowing the instructions.
n
Set Ethernet parameters
The dialog field for pre-setting an Ethernet address can be found in 'Start è Settings
è Network and Dial-up Connections'. The default setting is address assignment via
DHCP.
n
System properties (System)
Here you receive information about the version of the current Windows
system, the memory load and sharing (alterations here are not accepted into the reg-
istry) and the copyright. The register Device Name allows you to change the device
name that is shown during Ethernet communication for instance.
Please note that changes are set back after PowerOFF-PowerON. To
store them permanently into the registry file you have to store them
explicitly. For this call 'Start è Programs è KuK_Tools è KuK Tools'
[Store].
The dialog window where to configure the integrated MPI interface can be found under
'Start è Settings è Control Panel è MPI Configuration'.
n
HSA
Here you set the highest MPI address (highest station address). Within a MPI network
the highest MPI address must be identical!
n
TS
With TS (this station) you set the local MPI address for the Touch Panel.
n
Baud Rate
Enter here the transfer velocity of your MPI net. The baud rate has to be identical for
every MPI participant within the network. According to the Baud Rate the network
parameters are set.
Operating system WindowsÒ Embedded CE 6.0 Prof. > Structure
Deployment Touch Panel
Ò
operating
Ò
,
31