8
FISCO Ex ic IIC T4 Gc
1. The apparatus is to be installed in an enclosure which maintains a minimum ingress
protection rating of IP54 and meets the enclosure requirements of EN 60079-0 and
EN 60079-11.
NOTE:
All MTL fieldbus power supplies are designed to protect the fieldbus trunk from transient
disturbances on the DC power feed and will meet the requirements of maintaining transient
disturbances below 140% of the rated voltage.
8 .3

Inspection and maintenance

a) Inspection and maintenance should be carried out in accordance with European,
national and local regulations which may refer to the standard EN 60079-17 . In
addition specific industries or end users may have specific requirements which
should also be met.
b) Access to the internal circuitry must not be made during operation.
8 .4

Repair

This product cannot be repaired by the user and must be replaced with an equivalent
certified product.
.
8 .5

Marking

Each device is marked in compliance with the Directive.
This information applies to products manufactured during or after the year 2011.
Typical certification marking
For F3xx
For F3xx-V2
For details of FM and IECEx approvals see Sections 9 & 10.
NOTE
INM F300 Rev 9