Mean Well LCM-25KM Installation Manual

Advertisement

Quick Links

110
M
M

Features

180~277VAC input only
Built-in active PFC
Output current level selectable by DIP switch
Built-in
KNX
interface and push dimming function
Power supply synchronization function up to 10 units

Wiring

Housing with cable clamp for remote installation
Use wires with an adequate cross-section (see 5)
Use suitable mounting tools to do the wiring and mounting (see 5)
Use a
MCB
(miniature
circuit breaker) with an adequate current rating to protect the lighting system (see 6)
Environmental limitations
Maximum ambient temperature must not exceed 60
Always allow adequate ventilation clearances, 50mm, around the unit in use to prevent it from overheating
Only install the unit in interior environments
Cautions
This unit must be installed by a qualified electrician
It's not suitable to connect DC/DC constant current drivers as the output loads

Settings and connections

1. Output Current Level Settings

The LCM can provide various output currents by setting the DIP switch. The settings of the DIP switch are shown in the tables below.
LCM-25KN
Voltage
Selectable
1
2
range
Current
---
---
6-54V
350mA
---
6-50V
500mA
ON
6-42V
600mA
ON
ON
6-36V
700mA*
ON
ON
6-28V
900mA
ON
ON
6-24V
1050mA
ON
ON
Note : 1.Factory default setting is 700mA.
2.Output voltage and output wattage must not exceed the rated values.
Terminal blocks assignment for LCM
105mm

2. Connection of LED Lamps

Press down the "push button" by a slotted screw driver to insert or remove the cable.
Attention: Always connect LED lamps first before connect to 230Vac mains to avoid damage of LED!
LCM-25
KN
installation manual
SELV
3
4
5
6
---
---
---
---
---
---
---
---
---
---
---
---
---
---
ON
ON
---
ON
ON
ON
ON
ON
ON
ON
23mm
6
5
4
3
2
1
ON
KNX+
KNX-
+SYNC
4
3
-SYNC
2
-V
1
+V
3
PUSH
2
AC/N
1
AC/L
4
3
Vo-
2
1
Vo+
3
2
AC/N
NEUTRAL (Blue or white)
AC/L
1
LIVE (Brown or black)
http://www.meanwell.com
18
Class power unit, ungrounded
Full plastic case enclosed
No load power consumption <0.5W
Protections: Short circuit / Over temperature
3 year warranty
Suitable for intelligent LED lighting
Functions: Manual dim, operation hours,
power consumption feedback, log/linear curve selection...etc
2
1
MEAN WELL
2019/12/3
ISSUE

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the LCM-25KM and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Mean Well LCM-25KM

  • Page 1 2. Connection of LED Lamps Press down the "push button" by a slotted screw driver to insert or remove the cable. Attention: Always connect LED lamps first before connect to 230Vac mains to avoid damage of LED! MEAN WELL 2019/12/3 ISSUE...
  • Page 2 Suggested push-down strength ----- 6. Suggested Maximum Number of the LCM Units that can be Connected to a MCB ( miniature circuit breaker) at 230Vac MEAN WELL Model 2019/12/3 LCM-25KN ISSUE Note: These calculated values are based on MCB S201 series manufactured by ABB.

Table of Contents