Heat Delay Setup; Optional Vav Control Board Flash Codes; Heat Delay; Vav Control Board Flash Codes - York SUNLINE MagnaDRY DR240 Installation Manual

Gas/electric single package air conditioners
Hide thumbs Also See for SUNLINE MagnaDRY DR240:
Table of Contents

Advertisement

HEAT DELAY SETUP

Enter the Option Setup mode by pushing the
OPTION SETUP / STORE button, and holding it for
at least 2 seconds.
The green status LED (Option Byte) will be turned
on and the red status LED (Heat Delay) is turned
off.
Press the COMM SETUP / SELECT button to tog-
gle into the Heat Delay Setup, the green LED will
turn off and the red LED for Heat Delay will turn on.
The 8, 4, 2 and 1 LEDs will then show the status of
the Heat Delay, (See Table 37). Press the UP or
Down button to change the LED status to corre-
spond to the desired Heat Delay Value.
To save the current displayed value, push the
OPTION SETUP / STORE button and hold it for at
least 2 seconds. When the value is saved, the red
LED will flash a few times and then normal display
will resume.
NOTE: While in either Setup mode, if no buttons are
pushed for 60 seconds, the display will revert
to its normal display, exiting the Option Setup
mode. When saving, the control board only
saves the parameters for the currently dis-
played mode (Option Byte or Heat Delay).
TABLE 37: HEAT DELAY
Heat
Heat
Fan On
Fan Off
LED 8
Delay
Delay
60
180
60
90
60
60
60
30
45
180
45
90
45
60
45
30
30
180
30
90
30
60
30
30
0
60
0
30
0
10
Non-std
Non-std
Subject to change without notice. Printed in U.S.A.
Copyright © 2008 by Johnson Controls, Inc. All rights reserved.
Red
Red
Red
LED 4
LED 2
On
On
On
On
On
On
On
On
Off
On
On
Off
On
Off
On
On
Off
On
On
Off
Off
On
Off
Off
Off
On
On
Off
On
On
Off
On
Off
Off
On
Off
Off
Off
On
Off
Off
On
Off
Off
Off
Off
Off
Off
Johnson Controls Unitary Products

OPTIONAL VAV CONTROL BOARD FLASH CODES

Flash codes are also utilized by the VAV add-on board
to aid in troubleshooting optional VAV applications.
Flash codes are displayed by a red LED located near
the center of the board using a short on/off cycle
(approximately 200-ms on and 200-ms off).
To verify that the board is functioning correctly, the
LED will display a repetitive 1 second on, 1 second off
"heartbeat". Do not confuse this "heartbeat" with the
error flash codes shown in the table below. To prevent
confusion, a 1-flash, flash code is not used.
TABLE 38: VAV CONTROL BOARD FLASH CODES
FLASH CODE
On Steady
1 Flash
2 Flashes
3 Flashes
4 Flashes
5 Flashes
6 Flashes
7 Flashes
8 Flashes
9 Flashes
10 Flashes
11 Flashes
12 Flashes
13 Flashes
Red
14 Flashes
LED 1
15 Flashes
On
OFF
Off
On
TABLE 39: REHEAT CONTROL BOARD FLASH
Off
CODES
On
Off
FLASH CODES
On
On Steady
Off
1 Flash
On
Off
2 Flashes
On
Off
3 Flashes
On
OFF
Off
On
Off
5005 York Drive
Norman, OK 73069
DESCRIPTION
Control Failure
Not Applicable
Loss of Communication with UCB
Space Sensor Failure
SAT Sensor Failure
RAT Sensor Failure
OAT Sensor Failure
OH Sensor Failure
RH Sensor Failure
IAQ Sensor Failure
OAQ Sensor Failure
APS Switch Failure
Limit 2 Switch Open
Purge
VFD Input Failure
Dirty Filter Switch
No Power or Control Failure
DESCRIPTION
This is a Control Failure
Not Applicable
Hot Gas Reheat is on with Y1 Output
(No Call for Cooling)
Y1, Y2, and Hot Gas Reheat is on because of
a call for Y1 and Humidistat. See alt operation
No Power or Control Failure
284811-YIM-C-1008
Supersedes: 284811-YIM-B-0707