PATTERN 3
START PATTERN 3
See table 3:
Is it possible to lead a chimney
outside the building respecting the maximum
chimney length?
No
3b
You CANNOT install the unit in the room. Place the unit in a larger
room.
Tables for PATTERN 1, 2 and 3
Table 1: Minimum floor area
Take the following into account
• For intermediate refrigerant charges, use the row with the higher value. Example: If the refrigerant charge is 3.5 kg, use the row of 3.65 kg.
• For intermediate release heights without chimney, use the column with the lower value. Example: If the release height without chimney is
2.30 m, use the column of 2.25 m.
Charge (kg)
1.95 m
3.25 kg
8.51 m²
3.45 kg
9.59 m²
3.65 kg
10.73 m²
3.85 kg
11.94 m²
4.05 kg
13.22 m²
Table 2: Minimum release height
Take the following into account:
• For intermediate floor areas, use the column with the lower value. Example: If the floor area is 7.25 m², use the column of 6.00 m².
• For intermediate refrigerant charges, use the row with the higher value. Example: If the refrigerant charge is 3.5 kg, use the row of 3.65 kg.
• (*): The release height of the unit without chimney (minimum 1.95 m) is already higher than the minimum required release height. => OK (no
chimney needed).
Charge (kg)
3.25 kg
3.45 kg
3.65 kg
3.85 kg
4.05 kg
ELBH/X12E
Daikin Altherma 3 R MT W
4P708482-1 – 2023.03
Yes
Minimum floor area (m²)
2.05 m
2.15 m
2.25 m
7.70 m²
7.00 m²
6.39 m²
8.68 m²
7.89 m²
7.20 m²
9.71 m²
8.83 m²
8.06 m²
10.81 m²
9.82 m²
8.97 m²
11.96 m²
10.87 m²
9.93 m²
Minimum release height (m)
4.00 m²
6.00 m²
3.53 m
2.35 m
3.75 m
2.50 m
3.96 m
2.64 m
4.18 m
2.79 m
4.40 m
2.93 m
3a
You can install the unit in room A if you lead the chimney outside
the building.
A
Release height without chimney (m)
2.35 m
2.45 m
2.55 m
6.01 m²
5.76 m²
5.54 m²
6.60 m²
6.12 m²
5.88 m²
7.39 m²
6.80 m²
6.28 m²
8.22 m²
7.57 m²
6.98 m²
9.10 m²
8.37 m²
7.73 m²
Floor area (m²)
8.00 m²
10.00 m²
2.01 m
(*)
2.14 m
(*)
2.26 m
2.02 m
2.38 m
2.13 m
2.51 m
2.24 m
4 Unit installation
2.65 m
2.75 m
2.85 m
5.33 m²
5.13 m²
4.95 m²
5.65 m²
5.45 m²
5.26 m²
5.98 m²
5.76 m²
5.56 m²
6.47 m²
6.08 m²
5.87 m²
7.16 m²
6.65 m²
6.19 m²
12.00 m²
14.00 m²
(*)
(*)
(*)
(*)
(*)
(*)
(*)
(*)
2.05 m
(*)
Installation manual
2.95 m
4.78 m²
5.08 m²
5.37 m²
5.67 m²
5.96 m²
9