11.12.4 Indication of a service warning

A service warning is an exceptional event and requires the attention of the operator/service technician. The dryer will
not be stopped.
When a service warning is active, the
When a service warning is no longer active but not reset yet (so it has been stored)
In both cases the display shows the dew point temperature and the service warnings which are active or which are no
longer active but not yet reset.
Service warnings are NOT automatically reset.
To RESET the service warning, the
+
buttons for three seconds. Only the stored service warning will be reset. Service warnings which
are still active continue to be indicated by the
NOTE: the operator/service technician must check the dryer and eliminate the problem that caused the service
warning.
Service warning

11.12.5 Indication of an alarm

An alarm is an exceptional event which, to avert damage from to the machine and the operator, always leads to the
dryer stop.
When an alarm is active, the
When an alarm is no longer active but not reset yet (so it has been stored)
the dryer remains OFF).
In both cases the display shows
Alarms are NOT automatically reset.
To RESET the alarm, the
buttons for three seconds. Only the stored alarm will be reset. Alarms which are still active continue to be
indicated by the
Led flashing.
The dryer will start automatically subsequent to the reset of the alarms.
NOTE: the operator/service technician must check the dryer and eliminate the problem that caused the alarm.
Alarm
DRYPOINT® RA CT 200-500 NA 3PH
Led flashes.
Led must be continuously on (not flashing), keep pressed simultaneously
Led flashing.
HdP – High dew point: dew point too high, higher than the adjusted HdS value
LdP – Low dew point: dew point too low
Setting T1< -1°C (30°F) delay five minutes / reset T1> -0.5°C (31°F)
SrV - Service: maintenance service time expired SrV
LED flashes.
and the alarms which are active or which are no longer active but not yet reset.
Led must be continuously on (not flashing), keep pressed simultaneously
LP – Low pressure: the refrigerant low-pressure switch LPS has tripped.
Hdt – High outlet temperature: compressor outlet temperature outside the safety limit
Setting T2> 110°C (230°F) delay one minute / reset T2< 90°C (194°F)
ICE - ICE / Icing: Temperature in the exchanger (probe T1) is too low and leads to icing
of the condensate.
Setting T1< -2°C (28°F) delay one minute / reset T1> 0°C (32°F)
toC – Too many Cycles : compressor has been cycled On/OFF unusually too often
(stopped more than 5 times before reaching its minimum ON time)
PF1 – Probe 1 failure: failure probe T1
PF2 – Probe 2 failure: failure probe T2
Led is continuously on.
Description
Led is continuously on (in any case,
Description
Technical description
+
25