Dmc 18 Electronics (Control Unit Compressed-Air Dryer); Switching The Dryer On; Switching The Dryer Off; Indication Of The Operating Parameters - Beko DRYPOINT RAX 125 NA-E-OB Series Instructions For Installation And Operation Manual

Compressed air refrigeration dryer
Table of Contents

Advertisement

Technical description

13.12 DMC 18 electronics (control unit compressed-air dryer)

Set
DISPLAY
The DMC18 controls the alarms and the settings of the dryer operation and of the BEKOMAT drain.

13.12.1 Switching the dryer on

Connect the dryer to the electric mains and switch it on via the ON/OFF switch (pos. 1 Section 11.1).
During normal operation, the display shows the dew point temperature.
The condensate drain test is always possible via the

13.12.2 Switching the dryer off

Switch the device off via the ON/OFF switch (pos. 1 Section 11.1).

13.12.3 Indication of the operating parameters

During normal operation, the display shows the dew point temperature (in °C or °F).
Set
Press the
button and keep it pressed to display the
dew point).
Press the
button and keep it pressed to display the hours remaining until the next maintenance.
Set
Press the
+
dryer.
Note:
The temperatures are indicated in °C or °F (LED
The total operating hours and the hours until the next maintenance are indicated in the field 0...999 hours, and
in thousand hours from 1.0 hours onwards (example: when the display shows 35, this means 35 hours and
when the display shows 3.5, this means 3,500 hours).

13.12.4 Indication of a service warning/service alarm

A service warning/alarm is an exceptional event and requires the attention of the operator/service technician. The dryer
will not be stopped.
When a service warning/alarm is active, the
The display successively shows the dew point temperature and the active service warnings/alarms.
Service warnings/alarms are automatically reset as soon as the problem has been eliminated, except for
(maintenance time expired), where manual resetting is required (press the
least 20 seconds).
NOTE: the operator/service technician must check the dryer and eliminate the problem that led to the activation
of the service warning.
Service warning alarm
NOTE: when the dryer is switched on but no system pressure is applied, the
appear.
26
buttons and keep them pressed to display the total number of operating hours of the
LED flashes.
PF – Probe failure: failure temperature probe
HdP – High dew point: dew point too high, higher than the adjusted HdS value.
LdP – Low dew point: dew point too low, lower than the adjusted LdS value.
drA - Drain: failure Bekomat IF condensate drain - Delay 20 minutes
SrV - Service: maintenance service time expired SrV
Led - temperature in °C
Led - temperature in °F
Led – drain ON
Led – alarm/service
Button – access configuration menu
Set
Button – decrease / service
Button – increase / drain test
button.
parameter (alarm release temperature at a high
or
is on).
button and keep it pressed for at
Description
DRYPOINT® RAX 20-500 NA 1ph UL
drain trouble indication may