Installation
8.7

Electrical connections

Danger!
Supply voltage!
The connection to the electric mains should only be carried out by qualified skilled personnel and must
correspond to the legal provisions in force in your region.
Before connecting the unit to the electrical supply, verify the data nameplate for the proper electrical information.
Voltage tolerance is +/- 10%.
The installer is responsible for supplying and installing the power cable. Be sure to provide the proper fuses or
breakers based on the data information located on the nameplate.
RA VSD 800-1250
A residual-current device (RCD) with In =0.3A Class B
is suggested. The cross section of the power supply
cables must comply with the consumption of the dryer,
while
keeping
into
temperature, the conditions of the mains installation, the
length of the cables, and the requirements enforced by
the local Power Provider.
Compressor and fan(s) proper rotation direction are
managed automatically by the drivers.
It is not necessary to observe the phases sequence
when connecting the power cable to the main switch.
Danger!
Supply voltage and missing earth connection!
Important: ensure that the plant is connected to earth.
Do not use plug adapters at the power plug.
Possible replacement of the power plug must only be carried out by a qualified electrician.
Note!
This dryer is not suitable for employment on IT-systems.
This dryer is not suitable for employment on grounded-delta systems
 
18
account
also
the
ambient
RA VSD 1500-2500
DRYPOINT® RA VSD 800-2500