11.15.5 WARNING condition

A WARNING is an irregular event that must be flagged to operators/maintenance technicians. It does not jeopardise
the safety of the machine/operators, with the exception of the HdS parameter (STOP dryer due to high dew point),
which can be set to stop the dryer.
In the presence of a Warning the status bar shows a description of the event and turns flashing orange. In this
condition it is not possible to clear the Warning as the cause is still present.
When a Warning is no longer active but has not been cleared, the status bar shows a description of the event and is
permanently lit (orange). In this condition the Warning can be cleared as the cause has been removed.
With dryer operating: the presence of one or more Warnings is flagged on
the display with the status bar changing from green to orange. If there are
several active anomalies simultaneously, the status area displays them in
order.
When the dryer is off: one or more Warnings are not highlighted on the
display, other than the W11 Warning "Low ambient temperature" which
automatically clears.
It is only when the operator wants to start the dryer with the
control unit still enables the dryer to be started in the presence of a Warning,
and displays the Warning status by changing the colour of the status bar
(orange).
Clearing a Warning:
1- Touch the screen on the status bar where the Warning is shown.
2- Press
to confirm the Warning is to be cleared, or
clearing.
NOTE After clearing Warnings the operator/maintenance technician must verify/solve the problem that caused the
Warning with the dryer.
Warnings never clear automatically, with the exception of Warning no. W5 (malfunction of electronic condensation
drainer), which is factory-set to enable automatic clearing setting.