SYMPTOM
Blinking orange status area: one or more alarms are active. The touch screen display shows
Electronic
the ID code and description of the active alarm.
controller DMC55
Steady orange status area: one or more alarms need to be cleared. The touch screen display
in fault status
shows the ID code and description of an inactive alarm which needs to be cleared.
(orange colour
Refer to the Troubleshooting list above for possible causes and solutions.
status area)
Refer to the table under the "Fault condition" section to find the process value limits for the
following faults.
DRYPOINT® RA VSD 800-2500
POSSIBLE CAUSE - SUGGESTED ACTION
W1 - Low Dew Point: Dew Point T1 temperature too low - see specific fault
W2 - High Dew Point: Dew point T1 temperature too high (higher than the value set in
parameter HdA) - see specific fault
W3 - Probe Fault T2: BT2 temperature probe failure - check the electric wiring or replace
the probe.
W4 - Probe Fault T3: BT3 temperature probe failure - check the electric wiring or replace
the probe.
W5 - Drainer: ELDn condensate drain does not work properly (ALARM contact open) -
see specific fault. This fault could occur with dryer running but without compressed air
flow.
W6 - Programmed Service: Maintenance warning time expired (exceeding the value set
in parameter SrV) - carry out the programmed maintenance and reset the hour counter
W7 - High Discharge Temperature: Compressor discharge T4 temperature too high, but
within the safety limits - see specific fault
W8 - High Evaporating Pressure: Evaporating pressure too high - see specific fault
W9 - Low Condensing Pressure: Condensing pressure too low - see specific fault
W10 - High Condensing Pressure: Condensing pressure too high - see specific fault
W11 - Low ambient temperature: Room temperature detected by BT5 probe too low -
restore nominal conditions or replace the probe.
W12 - High ambient temperature: Room temperature detected by BT5 probe too high -
restore nominal conditions or replace the probe
W13 - Probe Fault T5: BT5 temperature probe failure - check the electric wiring and/or
replace the probe
W14 - Low inlet temperature: Compressed air inlet temperature detected by BT2 probe
too low - restore nominal conditions or replace the probe
W15 - High inlet temperature: Compressed air inlet temperature detected by BT2 probe
too high - restore nominal conditions or replace the probe
Maintenance, troubleshooting, spare parts and dismantling