Electrical Connections; Condensate Drain; Start Up; Preliminary Operations - Beko DRYPOINT RA 200/AC NA Operating Manual

Refrigerating air dryer
Table of Contents

Advertisement

Start up

2.8.

Electrical connections

DANGER!
Supply voltage!
Qualified personnel should carry out connecting unit to the main power.
Be sure to check the local codes in your area.
Before connecting the unit to the electrical supply, verify the data nameplate for the proper electrical information.
Voltage tolerance is +/- 5%.
Dryers are supplied with a junction box.
Be sure to provide the proper fuses or breakers based on the data information located on the nameplate.
The mains socket must be provided with a mains magneto-thermal differential breaker (I∆n=0.03A), adjusted on the
basis of the consumption of the dryer (see the nominal values on the data plate of the dryer). The cross section of the
power supply cables must comply with the consumption of the dryer, while keeping into account also the ambient
temperature, the conditions of the mains installation, the length of the cables, and the requirements enforced by the
local Power Provider.
DANGER!
Mains voltage and missing earthing!
Important: ensure that the plant is earthed.
Do not use any socket adapters at the mains plug.
If the mains plug needs to be replaced, this must only be done by a qualified electrician
2.9.

Condensate Drain

DANGER!
Compressed air and pressurized condensate!
The condensate is discharge at the system pressure.
Drain line should be secured.
Never point the condensate drain line towards anybody.
The dryer comes already fitted with an electronically level controlled BEKOMAT condensate drain. Connect and
properly fasten the condensate drain to a collecting plant or container.
The drain cannot be connected to pressurized systems.
Don't dispose the condensate in the environment.
The condensate collected in the dryer contains oil particles released in the air by the compressor.
Dispose the condensate in compliance with the local rules.
We suggest to install a water-oil separator where to convey all the condensate drain coming from
compressors, dryers, tanks, filters, etc. We recommend ÖWAMAT oil-water separators for disperse
compressor condensate, BEKOSPLIT emulsion splitters for emulsified condensate.
3. Start up
3.1.

Preliminary Operations

CAUTION!
Exceeding of operating parameters!
Verify that the operating parameters match with the nominal values stated on the data nameplate of the dryer
(voltage, frequency, air pressure, air temperature, ambient temperature, etc.).
This dryer has been thoroughly tested, packaged and inspected prior to shipment. Nevertheless, the unit could be
damaged during transportation, check the integrity of the dryer during first start-up and monitor operation during the
first hours of operation.
Qualified personnel must perform the first start-up.
When installing and operating this equipment, comply with all National Electrical Code and any applicable
federal, state and local codes.
Who is operating the unit is responsible for the proper and safe operation of the dryer.
Never operate equipment with panels removed.