Error codes related to the CC-Link IE Field Network

This section describes CC-Link IE Field Network error codes. Communication errors refer to CC-Link IE Field Network
communication related errors and safety communication related errors. The ERR. LED does not turn on when a
communication error occurs.
Communication errors of the CC-Link IE Field Network are classified into the following two error types depending on the
operation of the D LINK LED performed at an error, and troubleshooting differs for each error type.
• Page 154 Communication errors where the D LINK LED flashes or turns off
• Page 155 Communication errors where the D LINK LED does not change
Communication errors where the D LINK LED flashes or turns off
The following table lists the communication errors of the CC-Link IE Field Network where the D LINK LED flashes or turns off
at an error. Troubleshoot these errors with the CC-Link IE TSN/CC-Link IE Field diagnostics of the engineering tool.
Error code
Classification
(hexadecimal)
D0E0H
Communication
error
D0E1H
Communication
error
D0E2H
Communication
error
D0E3H
Communication
error
D72AH
Communication
error
10 TROUBLESHOOTING
154
10.7 List of Error Codes
Error name
Description and cause
Station type mismatch
The module parameter of the master
station is incorrect or outside the range.
Own station reserved
The module parameter of the master
station is incorrect or outside the range.
Station No. already in
The station number switch setting is
use (own station)
incorrect.
Own station No. out of
The module parameter of the master
range
station is incorrect or outside the range.
Station number switch
A station number out of the setting range
out of range
(a value other than 1 to 120) is set.
Action
Change the station type of the module to the
remote device station in the "Network
Configuration Settings" of the master station.
• In the "Network Configuration Settings" of the
master station, cancel the reserved station
specification.
• Change the station number of the module to a
station number that is not reserved.
• Set a unique station number so that all stations
have a different station number.
• After taking the above action, power off and on
or reset all the stations where this error was
detected.
Add the station information of the module in the
"Network Configuration Settings" of the master
station.
Set the station number within the allowable range.