Quest CDG 174 Quest Dry Installation, Operation and Maintenance Instructions Installation, Operation and Maintenance Instructions – Read and Save These Instructions – This manual is provided to acquaint you with the dehumidifier so that installation, operation and maintenance can proceed successfully. Ultimate satisfaction depends on the quality of installation and a thorough understanding of this equipment.
Quest CDG 174 Installation, Operation and Maintenance Instructions Safety Precautions Read the installation, operation and maintenance instructions carefully before installing and operating this device. Proper adherence to these instructions is essential to obtain maximum benefit from your Quest CDG 174.
2.1 Transporting The Quest CDG 174 must always be upright when transported by vehicle. It may be tipped on to its handle and back for loading and moving by hand.
2.3 Electrical Requirements The Quest CDG 174 can be plugged into a grounded 15 Amp circuit. At 80°F, 60% RH, it draws 10 Amps. Due to the high percentage of a 15 Amp circuit’s capacity that the unit uses, the circuit should be dedicated to running it only. Amp draw decreases at lower loads and increases at higher loads.
3.1 Air Filter The Quest CDG 174 is equipped with a pleated fabric air filter that must be checked regularly. The standard filter is a MERV-11 high efficiency filter. Operating the unit with a dirty filter will reduce the dehumidifier’s capacity and efficiency and may cause the compressor to cycle off and on unnecessarily on the defrost control.
3.2 Storage There are two issues to consider when the Quest CDG 174 is stored between uses and both pertain to the water trapped in the unit: damage caused by freezing and biological growth. The effect of the trapped water can be greatly reduced if precautions are taken to remove as much as possible before storage.
Quest CDG 174 Installation, Operation and Maintenance Instructions The evaporator operates in a flooded condition, which means that all the evaporator tubes contain liquid refrigerant during normal operation. A flooded evaporator should maintain constant pressure and temperature across the entire coil, from inlet to outlet.
Page 9
Quest CDG 174 Installation, Operation and Maintenance Instructions Air mover does not run. Compressor runs briefly but cycles on and off. Loose connection in blower circuit Obstruction prevents impeller rotation 3. Defective air mover 4. Defective control board. Unit removes some water but not as much as expected.
Quest CDG 174 Installation, Operation and Maintenance Instructions 4.4 Refrigerant Charging If the refrigerant charge is lost due to service or leak, a new charge must be accurately weighed in. If any of the old charge is left in the system, it must be removed before weighing in the new charge. Refer to the unit nameplate for the correct charge weight and refrigerant type.
Installation, Operation and Maintenance Instructions 4.8 Gravity Drain Option If the condensate pump fails and cannot be replaced immediately, the Quest CDG 174 can be used by draining by gravity. Unplug the unit and remove the front cover. Push the plastic plug on the right side (see Fig. 4) out from inside the unit.
Quest CDG 174 Installation, Operation and Maintenance Instructions 6 Service Parts Item Description Part No. Item Description Part No. Top Cover 4035206 Condenser Coil 4028566 Top Cover Hinge 4027267 Condensate Pump 4034605-01 Wheel 12” Gray 4026304 Fan Motorized Impeller 4026657 Cotter Pin 3/32”...
Year One: Therma-Stor LLC warrants that, for one (1) year the Quest CDG 174 dehumidifier will operate free from any defects in materials and workmanship, or Therma-Stor LLC will, at its option, repair or replace the defective part(s), free of any charge.