INSTALLATION REQUIREMENTS

Review the following information before installing the unit:
• Do not install the indoor units near a direct source of heat such as
direct sunlight or a heating appliance.
• Allow sufficient space for airflow and unit servicing. See Fig. 6 —
on page 5 for the minimum required distances between the unit and
the walls or ceilings.
• Communication wiring must be at least 3 ft. (1m) away from all
electromagnetic interference (televisions, radios, etc.) sources.
Interference is still possible even if this distance is maintained.
• Ensure any hanger used is strong enough to withstand the unit's
weight.
• If the indoor unit is installed in an unconditioned space,
running for long periods of time when the temperatures are
outside the recommended indoor unit operation ranges, it is
recommended to seal all the corners of the indoor unit to
prevent any leakage and add insulation material (13/32 to 13/
16 in (10-20 mm)) to the entire surface of the indoor unit to
avoid condensation or heat transfer.
NOTE: Nuisance sweating may occur if the unit is installed in a
high humidity environment with low airflow.
Table 3 — Operating Range
OPERATING RANGE
MIN/MAX °F (°C)
Cooling
Indoor DB
62 / 90 (17 / 32)
Indoor WB
59 / 84 (15 / 29)
WARNING
PRODUCT INSTALLATION
• Installation must be performed by an authorized dealer or
specialist. A defective installation can cause water leakage,
electrical shock, or fire.
• The installation must be performed according to the installation
instructions. Improper installation can cause water leakage,
electrical shock, or fire. (In North America, installation must be
performed in accordance with the requirements of NEC or CEC
by authorized personnel only.)
• Contact an authorized service technician for repair or
maintenance of this unit. This appliance must be installed in
accordance with local codes.
• Only use the included accessories, parts, and specified parts for
installation. Using non-standard parts can cause water leakage,
electrical shock, fire, or unit failure.
• Install drainage piping according to the instructions in this
manual and in accordance with local codes. Improper drainage
may cause water damage to your home and property.
• For units that have an auxiliary electric heater, DO NOT install
the unit within 3 feet (1 meter) of any combustible materials.
• DO NOT install the unit in a location that may be exposed to
combustible gas leaks. If combustible gas accumulates around
the unit, it may cause a fire.
• DO NOT turn on the power until all work has been completed.
• When moving or relocating the system, consult experienced
service technicians for the disconnection and re-installation of
the unit.
NOTE: DO NOT install the indoor or outdoor units in a location
with special environmental conditions. For those applications,
contact your Ductless representative.
4
Securely install the indoor unit on a structure that can sustain its
weight. If the structure is too weak, the unit may fall and cause
personal injury, unit and property damage, or death.
DO NOT install the indoor unit in a bathroom or laundry room as
excessive moisture can short the unit and corrode the wiring.
Install the indoor and outdoor units, cables and wires at least 3.2 ft
(1m) from televisions, routers, computer equipment or radios to
prevent static or image distortion. Depending on the appliances, a
3.2 ft (1m) distance may not be sufficient.
If the indoor unit is installed on metal, it must be electrically
grounded.
Heating
32 / 86 (0 / 30)
Specifications subject to change without notice.
WARNING
CAUTION
IM-40MBAA-02