Toshiba BMS-SM1280ETLE Service Manual page 48

Smart manager with data analyzer
Table of Contents

Advertisement

13-5.Questions about functions
No.
1
What is the procedure to create a setting file?
2
How many air conditioners can be connected?
3
How many air conditioners can be connected?
4
How many central remote controllers can be
connected?
5
Is it possible to turn on or off the lighting equipment, fan
or any other manufacture's air conditioner?
6
Can a schedule timer be used together?
7
Can a touch screen-type air conditioning management
system be used together?
8
Can the BACnet system be used together?
9
Can the LONwork system be used together?
10
Can a device in the AI-NETwork series be connected? Not possible. Use an air conditioning management system supported for the
11
Up to how many PCs can be connected?
12
How many users can simultaneously access the
system?
13
Can the system connect to an intra-company LAN?
14
Is connection available via the Internet (WAN)?
15
Is connection available from a mobile phone?
16
Is it possible for Smart Manager with data analyzer to do
SMTP authentication on email server used for alarm email?
17
Can a tenant name or other names be changed?
18
Up to how many characters can be used for the name
of tenant, etc.?
19
How many items does the alarm history save?
20
How many days of power distribution data does the
system save?
21
Can data be maintained in case of power outage?
22
Does turning off the controller require any specific
operation?
23
Does turning off the controller stop the air conditioner? The air conditioner where the remote controller or wireless adaptor is
24
Does a scheduled operation work only if a PC remains
connected?
25
Does a PC need to remain connected to save power
distribution data?
26
Is it possible to know an air conditioner failure without
connecting a PC?
27
How many master schedules can be created?
28
How many billing schedules can be created?
Questions
Please read the Operating Instration of the Setting File Creation Software.
Up to 128 units of air conditioners can be connected. Note that up to 64 units
can be connected per TCC-LINK line.
Up to 64 units can be connected per TCC-LINK line. The controller has two
TCC-LINK lines, thus up to 128 units can be connected.
Up to 10 central remote control devices can be connected per TCC-LINK line.
The central control devices include a central remote controller, a schedule
timer, and an ON / OFF controller.
This is possible by connecting to the general devices control interface.
Possible. Note that schedule must be set so that it does not conflict with the
schedule setting from the browser.
Not possible. However, it is possible to use a touch screen-type air
conditioning management system together with a central control device other
than the Web-based central remote controller.
Possible. However, it is possible to use BACnet system together with a
central control device other than the Web-based central remote controller.
Possible. Check that it works.
AI-NETwork series.
Up to 4 users can simultaneously log on.
Up to 4 PCs can be simultaneously connected.
Without simultaneous connection, the number of PCs connected has no
limitation.
Possible. However, check with your network administrator if the connection
is available.
Not available.
Not possible.
You can use the Setting File Creation Software to change the name of a floor,
a tenant, an area, and an air conditioner. And Section changeover software
can change floor, tenant, area, Monthly report tenant name.
For a floor name: 20 bytes,
for a tenant name: 30 bytes,
for an area name: 20 bytes, and
for an air conditioner name: 20 bytes.
It saves up to 1,024 items. If the alarm history items exceed 1,024, the item
is deleted sequentially from the oldest one.
The system saves the 45 days of daily report files and the 3 months of
monthly report files.
Data will be backed up before being saved. If power outage occurs during the
data saving, the backup data is restored, thus the data is protected.
No specific operation is necessary.
connected does not stop when the controller is turned off.
An air conditioner other than the above stops.
No. Because the schedule data are saved inside the controller, the PC does
not need to remain connected.
No. Because the power distribution data are saved inside the controller, the
PC does not need to remain connected.
An alarm can be set to go off with a buzzer or other means connected to the
alarm external output of no-voltage A contact.
Up to 32 schedules can be created for each master schedule and billing
schedule.
48