Phasing; Blower Rotation; Belt Tension; Supply Air Limitations - York MagnaDRY DK-07 Series Installation Manual

Single package air conditioners and single package gas/electric units
Table of Contents

Advertisement

PHASING

MagnaDRY™ DK units are properly phased from the factory.
If the unit does not start up, the electrical connection to the
unit may be misphased. If unit is equipped with a Phase Mon-
itor check the phase monitor for a Red LED, indicating a mis-
phase. Change the phasing of the Field line connection at
the Factory or Field Supplied Disconnect to obtain a
Green LED on the Phase Monitor. (Scroll compressors oper-
ate in only one direction. If the scroll is drawing low amper-
age, has similar suction and discharge pressures, or
producing a high noise level, the scroll is misphased.)
Scroll compressors require proper rotation to oper-
ate correctly. Units are properly phased at the fac-
tory. Do not change the internal wiring to make the
blower condenser fans, or compressor rotate cor-
rectly.

BLOWER ROTATION

Check for proper supply air blower rotation. If the blower is
rotating backwards, the line voltage at the unit point of power
connection is misphased (See 'PHASING').
TABLE 18: SUPPLY AIR LIMITATIONS
Unit
Minimum
-07
-10
-12

BELT TENSION

The tension on the belt should be adjusted as shown in Fig-
ure 30.
Johnson Controls Unitary Products
Maximum
2250
3750
3000
5000
3750
6250
A
C*
* NEVER LOOSEN
A
B
FIGURE 30 - BELT ADJUSTMENT
Procedure for adjusting belt tension:
1. Loosen six nuts (top and bottom) A.
2. Adjust by turning (B).
3. Never loosen nuts (C).
4. Use belt tension checker to apply a perpendicular
force to one belt at the midpoint of the span as
shown. Deflection distance of 4mm (5/32") is
obtained.
To determine the deflection distance from normal
position, use a straight edge from sheave to sheave
as reference line. The recommended deflection
force is as follows:
Tension new belts at the max. deflection force rec-
ommended for the belt section. Check the belt ten-
sion at least two times during the first 24 hours of
operation. Any retensioning should fall between the
min. and max. deflection force values.
5. After adjusting retighten nuts (A).
335224-BIM-B-1208
A
SPAN LENGTH
DEFL. FORCE
31