Self-Calibrating AC Current Switch with Solid State Outputs
IN ORDER TO AVOID ELECTRIC SHOCK OR OTHER POSSIBLE INJURY:
• DO NOT USE THIS PRODUCT FOR HUMAN SAFETY APPLICATIONS.
IT WAS NOT DESIGNED, TESTED OR RECOMMENDED FOR THIS
USE.
• DO NOT USE THIS PRODUCT IN HAZARDOUS LOCATIONS (E.G.
EXPLOSIVE ATMOSPHERES). IT WAS NOT DESIGNED, TESTED OR
RECOMMENDED FOR THIS USE.
• ENSURE THE PRODUCT IS PROPERLY WIRED FOR THE
APPLICATION. REFER TO THE SPECIFICATIONS AND WIRING
DIAGRAMS IN THIS MANUAL.
MODELS COVERED IN THIS MANUAL
Catalog Number
Description
ECS701SC
Solid Core, N.O., Over/Under Load
ECS700SC
Solid Core, N.O., Overload Only
ECS702SC
Solid Core, N.O., Underload Only
ECS711SP
Split Core, N.O., Over/Under Load
ECS710SP
Split Core, N.O., Overload Only
ECS712SP
Split Core, N.O., Underload Only
INTRODUCTION
The CurrentWatch™ ECS7 Series current
switches are designed for overload,
underload or operating window applications.
Upon sensing an average operating current,
the ECS7 Series self-learns and establishes a
limit-alarm trip point based on plus or minus
15 percent of the average expected current
being monitored. The ECS7 Series is available
in solid or split core housing styles.
The ECS7 Series magnetically isolated solid state output contacts are
rated for 0.30A @ 135V AC/DC. This "universal" output makes this
product especially well suited for PLC control systems or a variety of
load connections.
Eaton's current sensor family encompasses a broad range of products
for cost-effective monitoring, status, and predictive maintenance.
Downtime and costly repairs can be avoided by utilizing Eaton's
products and technology in your control systems.
Note: Unless otherwise specifi ed, the term "load" refers to the
current being monitored.
Effective: April 2010
Installation Instructions
CurrentWatch™ ECS7 Series Current Switches
WARNING
Questions? Call our Sensor Application Engineers at (800) 426-9184.
INSTALLATION
Considerations for all ECS7 Series models...
• Run wire to be monitored through the aperture (opening) in the
switch body.
• These switches can be located in the same environment as
motors, contactors, heaters, pull-boxes and other electrical
enclosures.
• Mounting can be done in any position or hung directly on a wire
with a wire tie.
• Be sure to leave at least one inch distance between sensor and
other magnetic devices.
Considerations for split-core models only...
• Press the tab in the direction
shown in the diagram to the right.
• After placing the wire in the
aperture, press the hinged portion
fi rmly downward until a click is
heard and the tab pops out fully.
• Keep split-core contact areas
clean. Silicon grease is factory applied on the mating surfaces to
prevent rust and improve performance. Be careful not to allow
grit or dirt into the grease in the contact area, particularly on core
mating surfaces of split core models. Sensor operation could be
impaired if mating surfaces do not have good contact. Check
visually before closing.
QUICK INSTALL GUIDE
The below steps can be followed to quickly install a CurrentWatch™
ECS7 Series switch.
1. Run the wire to be monitored through the aperture
2. Mount the sensor
3. Connect output wire to the solid state relay terminals
a. Use up to 14 AWG copper wires
b. Don't exceed output rating
4. Slide the Function Switch from "CLR" to "RUN"
5. Turn load "on", equipment is now energized and sensor is
calibrated
• Note: Refer to the LED Indication table on page two for switch
operation.
WIRING DIAGRAM
Connect control or monitoring wires to the sensor. Use up to 14 AWG
copper wire and tighten terminals to 7 inch-pounds torque. Be sure the
output load does not exceed the solid state output rating.
CAUTION! Incandescent lamps can have "cold fi lament inrush"
current of up to ten times their rated amperage. Use caution when
switching lamps.
AC or DC
Power
Monitored
Wire
P51922 Rev 04
Important:
Keep contact areas clean
AC or DC
Electrical Equipment Load
Use caution when
switching lamps
695000107
To open:
Press tab inward
towards hinge
Page 1

Advertisement

loading

Summary of Contents for Eaton CurrentWatch ECS7 Series

  • Page 1 7 inch-pounds torque. Be sure the output load does not exceed the solid state output rating. Eaton’s current sensor family encompasses a broad range of products CAUTION! Incandescent lamps can have “cold fi lament inrush”...
  • Page 2 P51922 Rev 04 695000107 SETPOINT ADJUSTMENT RANGES AND MAXIMUM AMPS The CurrentWatch™ ECS7 Series has an internal microprocessor Maximum Amps that “learns” your load characteristics and calibrates the setpoint and Housing Range Continuous 6 sec. 1 sec. setpoint window. Initial Calibration Solid Core 1.5-150A 500A...

This manual is also suitable for:

Currentwatch ecs701scCurrentwatch ecs700scCurrentwatch ecs702scCurrentwatch ecs711spCurrentwatch ecs710spCurrentwatch ecs712sp