Verifying The Settings - ABB RELION 670 Series Commissioning Manual

Line differential protection version 2.1 iec
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

Section 10
Testing functionality by secondary injection
IEC09000226 V1 EN-US
Figure 28: Operating principle and characteristic of the power swing detection function
Where:
RLdInFw =
RLdInRv =
X1OutFw =
X1OutRv =
10.4.9.1

Verifying the settings

Preconditions
The following output signal shall be configured to binary output available: ZOUT, measured
impedance within outer impedance boundary.
1.
Keep the measured current as close as possible to its rated value or lower. Keep it
constant during the test, but ensure that it is higher than the set minimum operating
current.
2.
Ensure that the maximum continuous current to the IED does not exceed four times its
rated value, if the measurement of the operating characteristics runs under constant
voltage conditions.
3.
Make the necessary connections and settings of the test equipment for test of point 1
according to figure 28.
106
X1OutFw
X1InFw
RLdOutRv
2
RLdInRv
X1InRv
X1OutRv
(settings parameters in italic)
RLdOutFw · kLdRFw
RLdOutRv · kLdRRv
X1InFw + (RLdOutFw - RLdInFw)
X1InRv + (RLdOutFw - RLdInFw)
ZL
X
3
j
1
RLdOutFw
4
1MRK 505 345-UEN B
j
R
RLdInFw
IEC09000226_1_en.vsd
Commissioning manual
M13888-11 v6