DOK-INDRV*-HCS02******-IT01-EN-P
Rexroth IndraDrive Drive Controllers Power Sections HCS02
5.2.8
L+ L-, DC Bus Connection
Function, Pin Assignment
●
Maximum allowed inductance: 100 µH (2 twisted single strands, 75 m
long)
●
Parallel line routing where possible
The control voltage supply is routed to the connection X13 from above:
1
Lines to control voltage supply
Fig.5-14:
Control Voltage Supply at X13
The input 0V is connected in conductive form to the housing po‐
tential. It is therefore impossible to use an insulation monitor at
+24V and 0V against housing.
WARNING
Before working on live parts: De-energize installation and secure power
switch against unintentional or unauthorized re-energization.
Wait at least 30 minutes after switching off the supply voltages to allow dis‐
charging.
Check whether voltage has fallen below 50 V before touching live parts!
The DC bus connection connects
●
several drive controllers to one another
●
a drive controller to additional components
HCS02.1E-W0012 drive controllers do not have a DC bus con‐
nection.
Bosch Rexroth AG
Lethal electric shock by live parts with more
than 50 V!
41/67
Instructions for Use