Technical description
3.3

Operating elements and displays

3.3.1

Cover

1
Fig. 2:
Design - top view
1
Cover screws
2
Automatic mode
3
Operating mode selector switch
4
Manual adjustment

3.3.2 DIP switches and LED

3
2
1
Fig. 3:
DIP switches and LED
1
DIP switches A (1-6)
2
DIP switches B (1-8)
3
LED
115802384-V01.10.2022
2
3
4
3.3.3

LED displays

LED display
LED lights up green
LED flashes green
LED lights up green + LED
flashes red quickly =
LED flashes orange
quickly
LED lights up green + LED
flashes red =
LED flashes orange
LED lights up red
LED flashes red
LED flashes red quickly
Meaning
Normal operation /
Automatic mode
Valve blocking protection
Safety end position
Initialisation (valve
adaptation)
Wire breakage with DIP
switch B5 ON and
2..10 V or 4..20 mA
and Yin < 1 V or 2 mA
Manual adjustment or
manual mode (Stop) /
Actuator does not follow
the control signal
Unsolvable blockade
Initialisation failed /
Actuator does not follow
the control signal
Operating voltage too low