Technical Data; Dimensions - oventrop Aktor M Operating Instructions Manual

Hide thumbs Also See for Aktor M:
Table of Contents

Advertisement

Aktor M
Technical description
3.4

Technical data

Technical data
Nominal voltage
Dimensioning
Switch-on current
Power consumption
Control
Cable cross-section
Stroke
Position feedback
Positioning speed
Positioning force
Sound power
Ambient temperature
Ambient humidity
10
24 V AC/DC ±10 %;
50/60 Hz
18 VA (AC); 9 W (DC) with
actuator heating: 24 VA
(AC); 12 W (DC)
max. 7 A, < 1 ms,
< 0.049 A²s *
Sleep mode: 1.6 VA (AC);
0.6 W (DC)
1.9 s/mm and 2.6 s/mm:
nominal: 9 VA (AC); 4.5 W
(DC)
5.5 s/mm and 9 s/mm:
nominal: 3 VA (AC); 1.5 W
(DC)
Floating signal (Open/
Stop/Closed); minimum
switch-on time 2 s
On/off signal (Open/
Closed) or modulating
control; alternatively
adjustable with voltage
signal 0(2)..10 V DC;
Re=100 kΩ; invertible or
with current signal
0(4)..20 mA; invertible
min. 0.75 mm²
max. 20 mm, automatic
stroke adaptation
0(2)..10 V DC; 5 mA for
0..100 % positioning
stroke; invertible; approx.
12.5 V signal in case of
fault or 0(4)..20 mA; Ri=
0.5 kΩ for 0..100 %
positioning stroke;
invertible; approx. 0 mA
signal in case of fault
Adjustable via DIP
switches (see page 34):
1.9 s/mm
2.6 s/mm
5.5 s/mm (factory setting)
9 s/mm
nominal 1000 N
approx. 38 dB(A) at
5.5 s/mm
0..55 °C
0..95 % r.h., non-
condensing
Protection type
Protection class
Mounting position
Maintenance
Weight
3.5

Dimensions

145
Ø 9
Ø 30
Ø 50
Fig. 4:
Dimensions
IP54 (upper half-sphere),
IP40 (lower half-sphere)
(see Fig. 5 on page 12)
III according to EN 60730
360°
Maintenance-free
1.45 kg
95
115802384-V01.10.2022

Advertisement

Table of Contents
loading

Table of Contents