Aktor M
Commissioning
6. Commissioning
6.1
Setting of the DIP switches
NOTICE
Damage to the actuator due to short circuit!
Touching conductive areas of the PCB with a
conductive tool can damage electronic
components.
!
Do not use conductive tools to adjust the DIP
switches.
6.1.1
DIP switches A
Fig. 24:
DIP switches A
0,2V
A
A
0,5V
Fig. 25:
Settings of DIP switches A
16
6
5
4
3
2
1
1,9s/2,6s
A1-A6
5,5s/9s
DIP
Function
ON
OFF
1
Hysteresis: 0,2 V (0.4 mA)
1
Hysteresis: 0,5 V (1 mA)
2
Feedback: absolute position
2
Feedback: relative position
3
Actuator heating: On (is switched
on at low temperatures)
3
Actuator heating: Off
4
Automatic mode: On
4
Automatic mode: Off
Function of the magnetic switch
active
5
Positioning speed 5.5 s/mm
6
5
Positioning speed 1.9 s/mm
6
5
Positioning speed 9 s/mm
6
5
Positioning speed 2.6 s/mm
6
Relative position:
Regardless of the set valve characteristic line, Yin
= Yout when reaching the control position.
Absolute position:
Depending on the set valve characteristic line,
Yout can deviate from Yin when reaching the
control position. Example equal-percentage
characteristic line: Yin = 4 V → Yout = 3.5 V
115802384-V01.10.2022