4.16 The Connecting of Central Control at IDU Terminals

This function allows the field connection of the AC-EZ central controller to the indoor unit communications
buss on Multi V 5.
■ Setting the function
Function
The Connecting of Central
Control at IDU Terminals
■ Option Selection
Setting
on
oFF
■ Detailed information
• This function is used with heat pump and heat recovery.
· Ask an authorized technician to setting a function.
232
_TROUBLE SHOOTING GUIDE BOOK
Option
Fn 19
on, oFF
Detail of function
AC EZ connection
Not setting (Default)
4.17 Compressor Input Current
This function is used when the current management is required by proportionally reducing the maximum
MFA specification of the product.
■ Setting the function
Function
Compressor Input Current
■ Option Selection
Compressor input
Setting
current limit (%)
oFF
-
op1
95
op2
90
op3
85
op4
80
op5
75
■ Detailed information
• This function is used with heat pump and heat recovery.
• All modes are a change in the setting impact.
• Since the MFA value is different for each HP and the value is limited proportionally, it does not
mean that the option value differs for each chassis.
(Maximum current value for each model is stored in EEPROM in main PC)
· Ask an authorized technician to setting a function.
· If do not use a function, set an off-mode.
· If use a function, capacity may go down.
Option
Fn 20
oFF, op1~op10
Compressor input
Setting
current limit (%)
op6
70
op7
65
op8
60
op9
55
op10
50