3.3 Precautions of Replacement
1. EEV should be judged correctly and replaced
2. Replaced EEV should be returned for cause analysis
3. Do not transfer heat to EEV body when welding
4. In case use the refrigerant after welding, be careful welding crack and the body damage
5. Be careful not to damage terminals when PCB is fastened
(Contact failure prevent )
6. PCB reset after replacement and check operation sound is normal
7. Vacuum at least 4 ~ 5 hours after welding.
8. After vacuum processing, please charge the refrigerant by calculating the additional amount of refrigerant
according refrigerant basic amount of the enclosed, outdoor unit charging factor, the pipe length.
162
_TROUBLE SHOOTING GUIDE BOOK
4. Solenoid Valve
Check that the output signal of the control board matches the operation of the solenoid valve.
4.1 Variable Path Valve
1. Basic control
- Base : Off
- Cooling mode : Open
- Low temperature cooling mode : Close
- Heating mode : Close
3. 솔레노이드 밸브
2. Failure Phenomenon
1. 가변 패스 밸브 상태
1) Open Failure
 상시 : Off 상태
: The upper EEV is closed and the refrigerant flow is blocked. So, the high pressure rises sharply
 제어 : 일반 냉방 운전 시 Open, 냉방 저온 운전 시 Close, 난방 운전 시 Close
→ CH34, High-pressure switch ON, Main PCB Off
2. 불량 현상
2) Close Failure
1) 밸브 Open 불량
: The refrigerant passing through the upper EEV does not go to the heat exchanger but enters
상부 EEV가 Close되어 냉매 흐름이 막히고 고압이 급격히 상승함
→ CH34 발생, 고압 스위치 작동 및 Main PCB Off 됨
accumulator through the variable path valve
→ Heat capacity decrease, Excessive temperature difference between upper / lower heat exchanger
2) 밸브 Close 불량
(more than 15 degrees)
상부 EEV를 통과한 냉매가 열교환기로 가지 않고, 가변 패스 밸브를 통해 Accum으로 들어감
→ 난방 운전 시 능력 저하, 열교환기 온도와 상/하부 열교환기 온도차 과다 발생 (15 ℃ 이상)