LG MULTI V 5 Manual Book page 53

Hide thumbs Also See for MULTI V 5:
Table of Contents

Advertisement

* Measuring resistance between each
terminal of compressor
* Measuring input voltage
N
R(L1)
S(L2)
T(L3)
* Compressor wire connection
Copyright ©2017 LG Electronics. Inc. All right reserved.
Only for training and service purposes
104
_TROUBLE SHOOTING GUIDE BOOK
- 120 -
LGE Internal Use Only
Error No.
Error Type
Error Point
Error No.
Error Type
Error Point
32*
Over-increase dis-
Compressor is off be-
Compressor is off because
Master 321
Over-increase discharge
charge temperature of
cause of over-increase
of over-increase discharge
32*
Slave1 322
temperature of inverter com-
inverter compressor 1
discharge temperature of
temperature of inverter
Slave2 323
pressor 1 at main outdoor unit
at main outdoor unit
compressor 1
inverter compressor 1
Slave3 324
33*
Compressor is off because
Over-increase dis-
Compressor is off be-
Master 331
Over-increase discharge
of over-increase discharge
Slave1 332
temperature of inverter com-
charge temperature of
cause of over-increase
33*
temperature of inverter
Slave2 333
pressor 2 at main outdoor unit
inverter compressor 2
discharge temperature of
compressor 2
Slave3 334
at main outdoor unit
inverter compressor 2
n Error diagnosis and countermeasure flow chart
Is the amount of
No
Is there pipe crack
refrigerant normal?
or trace of leakage?
[refer refrigerant part]
Yes
Yes
Weld / reconnect the cracked
portion and recharge refrigerant
No
Is the resistance of discharge
Replace discharge
temperature sensor normal?*
temperature sensor
* Resistance value of discharge temperature sensor
Yes
10°C = 362kΩ, 25°C= 200kΩ, 50°C= 82kΩ, 100°C= 18.5kΩ
Is EEV in
outdoor unit normal
No
at heating operation?
Replace outdoor unit EEV
[refer electric
component part]
Yes
Check another components
No
Is there pipe
and operation conditions
(strainer etc.) clogging?
/ Take measures
Yes
Replace strainer
Copyright ©2017 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Main Reasons
Main Reasons
1. Temperature sensor defect of in-
1. Temperature sensor defect of inverter com-
verter compressor 1 discharge pipe
pressor 1 discharge pipe
2. Refrigerant shortage / leak
2. Refrigerant shortage / leak
3. EEV defect
3. EEV defect
4. Liquid injection valve defect
4. Liquid injection valve defect
1. Temperature sensor defect of inverter com-
1. Temperature sensor defect of in-
pressor 2 discharge pipe
verter compressor 2 discharge pipe
2. Refrigerant shortage / leak
2. Refrigerant shortage / leak
3. EEV defect
3. EEV defect
4. Liquid injection valve defect
4. Liquid injection valve defect
Change the amount of
No
refrigerant
(Charge additive amount)
- 121 -
LGE Internal Use Only
105