LG MULTI V 5 Manual Book page 116

Hide thumbs Also See for MULTI V 5:
Table of Contents

Advertisement

3. Relative humidity effect
• In case of 35℃ (out air temp. condition)
- High humidity condition (RH 70 ~ 100%)
: Target coil temp. is lower than the standard humidity condition (RH 50~70%)
RH(%)
100~70
T
-T
air
target
<-0.5
A+0.4
-0.5 ≤ & < 0.5
A
0.5 ≤ & < 1.5
A-0.4
1.5 ≤ & < 2.5
A-0.8
2.5 ≤ & < 3.5
A-1.3
3.5 ≤
A-1.7
- Low humidity condition (RH 50 ~ 0%)
: Target coil temp. is less than the standard humidity condition (RH 50~70%)
RH(%)
100~70
T
-T
air
target
<-0.5
-0.5 ≤ & < 0.5
0.5 ≤ & < 1.5
1.5 ≤ & < 2.5
2.5 ≤ & < 3.5
3.5 ≤
230
_TROUBLE SHOOTING GUIDE BOOK
70~50
50~30
30~
Target Coil Temp.
A+1.2
A+0.8
A+0.4
A
A-0.4
A-0.8
70~50
50~30
30~
Target Coil Temp.
A+1.2
A+2.0
A+2.8
A+0.8
A+1.6
A+2.4
A+0.4
A+1.2
A+2.0
A
A+0.8
A+1.6
A-0.4
A+0.4
A+1.2
A-0.8
A
A+0.8
4.15 Humidity Reference
It is the function to set whether to use the humidity sensor. The outdoor unit considers the current outdoor
ambient humidity condition when making adjustments to the control values of the refrigeration cycle.
■ Setting the function
Function
Humidity Reference
■ Option Selection
Setting
on
oFF
■ Detailed information
• The humidity sensor's real time reporting of the outdoor ambient humidity level is used in the Ad-
vanced Smart Load Control (FN14), Comfort Cooling (ID10), and Intelligent Defrost - Smart Heating
(core logic) to prepare the system for changes in the building load.
• This function is used with heat pump and heat recovery.
• Heating, Cooling and Dry modes is a change in the setting impact.
• Cooling / Heating operation by using humidity sensor (Option "on")
- When used cooling operation of SLC function, it will improve energy efficiency because evapora-
tion temperature will be decreased
- When used heating operation in case of high humidity condition, deforest will be delayed because
target high/low pressure will be changed.
• Activation function by using humidity sensor (Option "on")
Multi V Ⅳ Multi V Ⅳ
Comfort
SLC
Cooling
cooling
Operation
Heating
X
Temperature
Consider-
ation
Humidity
X
X
· Ask an authorized technician to setting a function.
Option
Fn 16
on, oFF
Detail of function
Humidity sensor use
Not setting (Default)
Multi V 5
Multi V 5
Multi V 5
Dual Sensing
Dual Sensing
Increased heating
SLC
Comfort Cooling
time(Frost delay)
X
X
X
on
231