Idu Mode; Eev Pulse Of Non-Operating Idu In Heating - LG MULTI V 5 Manual Book

Hide thumbs Also See for MULTI V 5:
Table of Contents

Advertisement

5.12 Level Changes of CH200
It is a function to change CH200 error level.
■ Setting the function
Function
Level Changes of CH200
SE 14
■ Option Selection
Option
oFF
on
■ Detailed information
• This function is used with heat recovery.
• In case CH200 occurs because of communication error or individual breaker,
- Option is 'ON' → Changes to level4 and system on with CH200 display
- Option is 'OFF' → Changes to level3 and system off with CH200 display.
4.13 Level Changes of CH53
It is a function to change error level in the state of CH53.
■ Setting the function
Function
Level Changes of CH53
SE 15
■ Option Selection
Option
oFF
on
■ Detailed information
• This function is used with heat pump and heat recovery.
• In case CH200 occurs because of communication error or individual breaker,
- System operation is possible with level4 regardless of option setting.
- But after setting the option 'on', if CH21, 26, 29, or 116 occurs in the state of CH53, the system
will not operate because it is switched to level 1.
252
_TROUBLE SHOOTING GUIDE BOOK
Option
oFF, on
Detail of function
level 3 (CH200 display, system off, default)
level 4 (CH200 display, system on)
Option
oFF, on
Detail of function
level 4 (CH53 display, system on, default)
level 4 (CH53 display, system on)

6. IDU Mode

6.1 EEV Pulse of Non-operating IDU in Heating

It is the function to adjust EEV pulse of no IDU in heating.
■ Setting the function
Function
EEV Pulse of Non-operating
Id 1
IDU in Heating
■ Option Selection
seg1, seg2
1 ~ 64
• EEV pulse can be set in units of 10pls from 150 to 300pls. ('0': No setting)
■ Detailed information
• This function is used with heat pump and heat recovery.
• It is a function to take action in case of unusual issue in the field.
ex) EEV pulse of indoor unit is typically 80pls. (different by model)
① Claims due to refrigerant noise in non-operating IDU → EEV pulse ▼
② Refrigerant shortage cycle non-operating IDU during low load operation → EEV pulse ▲
·Ask an authorized technician to setting a function.
· If the EEV pulse is large, the risk of noise generation may increase and if the EEV pulse is small, the
risk of liquid accumulation may increase.
Option
seg1, seg2 : IDU No.
seg3, seg4 : EEV * 10pls
seg3, seg4
40 ~ 120 * 10pls
253