PRE-COMMISSIONING

Central Control

Central Controller Communications Limitations
Each type of Central Controller device is designed to communicate
with a limited quantity of indoor units. The quantity of indoor units
that can be connected to a single central control communications
cable, therefore, will be defined by the central control device on that
cable with the smallest Maximum Indoor Unit Quantity as shown at
right.
Group Number
If the building operator wants to know which indoor units are on each water source unit, and multiple systems serve a building:
• Assign a Group Number to each system. If there are more than 16 indoor units on a system, multiple Group Numbers may be necessary.
If the building owner wants to know which indoor units are on each floor:
• Assign a different group number for each floor. If there are more than 16 indoor units on a floor, multiple Group Numbers may be
necessary.
Member Number
Can be assigned at will or for example, can follow the room layout on each floor.
For each LG Central Controller product provided on the project, devise a central control address schedule and assign a central control ad-
dress to each indoor unit(s) Hydro Kit(s), and ERV(s) units. Record this central control address for each component in the column provided
on the Pre-commissioning Device Configuration Worksheet.
Upload Central Control Address to the Indoor Units
For all ducted, vertical and floor standing indoor units, the central control address must be assigned using a wired zone controller. Wall-
mount, ceiling cassette, ceiling suspended, and the wall/ceiling convertible indoor units, the central control address can be assigned using a
wireless handheld controller or a wired zone controller.
Power Up All Indoor Unit PCBs
Turn the disconnect for each indoor unit to the "ON" position. DO NOT turn the unit ON (on/off button remains off).
68
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Table 31: Central Controller Indoor Unit Connection Limitations.
Central Control Device
AC EZ
AC Smart II
AC Smart II with Expansion Kit
AC SMART Premium
LonWorks Gateway
BACnet Gateway
Advanced Control Platform
Maximum Indoor Unit Quantity
32
64
128
128
64
256
256