Table 14. Particulate contamination specifications (continued)
Particulate contamination
Conductive dust
Corrosive dust
Table 15. Gaseous contamination specifications
Gaseous contamination
Copper coupon corrosion rate
Silver coupon corrosion rate
NOTE:
Maximum corrosive contaminant levels measured at ≤50% relative humidity.
Operating system
Your Precision 7920 Rack supports the following operating systems:
● Windows 11 Pro, 64-bit
● Windows 11 Pro for Workstations, 64-bit
● Windows 10 Pro, 64-bit
● Windows 7 Pro, 32-bit (downgradable)
● Windows 7 Pro, 64-bit (downgradable)
● RHEL 8.0
● Ubuntu 16.04 LTS, 64-bit
System information label
Precision 7920 Rack – Front system information label
Figure 3. LED Behavior, Express Service Tag, Configuration and Layout
Specifications
NOTE:
Air entering the data center must have MERV11 or MERV13
filtration.
Air must be free of conductive dust, zinc whiskers, or other
conductive particles.
NOTE:
This condition applies to data center and non-data center
environments.
● Air must be free of corrosive dust.
● Residual dust present in the air must have a deliquescent point less
than 60% relative humidity.
NOTE:
This condition applies to data center and non-data center
environments.
Specifications
<300 Å/month per Class G1 as defined by ANSI/ISA71.04-2013.
<200 Å/month as defined by ANSI/ISA71.04-2013.
Product Overview
19