Start-Up, Calibration And Operation Of The Burner; Notes On Safety For The First Start-Up; Combustion Adjustment; Nozzles Installation - Riello RDB1 Firebird Oven 12 kW Installation, Use And Maintenance Instructions

Kerosene burner
Table of Contents

Advertisement

8

Start-up, calibration and operation of the burner

8.1

Notes on safety for the first start-up

The first start-up of the burner must be carried out
by qualified personnel, as indicated in this manual
and in compliance with the standards and regula-
tions of the laws in force.
WARNING
8.2

Combustion adjustment

In conformity with Efficiency Directive 92/42/EEC the application
of the burner on the boiler, adjustment and testing must be car-
ried out observing the instruction manual of the boiler, including
verification of the CO and CO
their temperatures and the average temperature of the water in
the boiler.
Combustion air is drawn in from outside, meaning
there may be notable changes in temperature,
which can affect the percentage of CO
WARNING
You are advised to adjust CO
the graph featured.
Example: outside air temperature 10 °C, adjust
CO
to 11.6% (± 0.2%).
2
Nozzle
GPH
0.40
8.3

Nozzles installation

The burner complies with the emission requirements of the
EN 267 standard.
In order to guarantee that emissions do not vary, recommended
and/or alternative nozzles specified by the manufacturer in the In-
struction and warning booklet should be used.
It is advisable to replace nozzles every year dur-
ing regular maintenance operations.
WARNING
The use of nozzles other than those specified by
the
manufacturer
maintenance may result into emission limits non-
conforming to the values set forth by the
regulations in force, and in extremely serious
cases, into potential hazards to people and
objects.
CAUTION
The manufacturing company shall not be liable for
any such damage arising from nonobservance of
the requirements contained in this manual.
Start-up, calibration and operation of the burner
concentration in the flue gases,
2
.
2
in accordance with
2
Pump pressure
Angle
bar
80°HT
7.0
and
inadequate
Check the correct working of the adjustment, com-
mand and safety devices.
WARNING
D7052
Output
kg/h ± 4%
1.0
8.3.1

Nozzles recommended

– Danfoss type H - S - EH - ES
– Delavan type A - W
– Steinen type Q - S
Angle 60°: in most cases.
Angle 80°: in case of flame detachment, during ignitions at low
temperatures.
regular
19
GB
Outside air temperature (°C)
Air damper
adjustment
Set-point
5.0
Fig. 18
Tab. E
20083766

Advertisement

Table of Contents
loading

This manual is also suitable for:

20083657501t1k

Table of Contents