Daikin Comfort Flex CLIWP Series Control Manual page 10

Direct expansion unit with scroll compressor
Hide thumbs Also See for Comfort Flex CLIWP Series:

Advertisement

2. The I/O available on that L-IOB device are shown in the Inputs / Outputs table.
3. To adapt the I/O name, double-click on the name in the Name column and edit it, e.g. 'RoomTemp'.
4. Select (or multi-select) an I/O in the list of Inputs/Outputs and look at the list of Object Parameters below. These parameters can be
used to configure the I/O.
5. In the Data points tab, the data points for the I/O have been created. These data points can be used, for example, in the IEC61131
logiCAD program. For the inputs, the data point L1_x_UIand_Input will be used to read an input value and for the outputs the data point
L1_x_DOand_Output will be used to set an output value.
LOYTEC INPUTS AND OUTPUTS
NAME
High Pressure
Low Pressure
Outdoor Temp.
Return Temp.
Injection Temp.
Motor Saver
AP Vent. Condenser
AP Evaporator
AP Compressor
AC Free Cooling
Zone Temp.
cm-cliwp-eng
NOMENCLATURE
SENSOR TYPE
AP
N.O. Switch
BP
N.O. Switch
TEx
Thermistor 10KM II
TR
Thermistor 10KM II
TI
Thermistor 10KM II
MS
N.O. Switch
Apv
Relay 24 VAC
Apc
Relay 24 VAC
APdx
24 VAC Relay
ACf
0-10 VDC
TZ
Total points per Ctrl
I/O
AI
PHYSICS
UI-1
UI-2
UI-3
1
UI-4
1
UI-5
1
UI-6
DO-1
DO-2
DO-3
AO-1
3
10
Control
DI
AO
DO
SPD
(TRIAC)
(500 Pa)
1
1
1
1
1
1
1
LSTAT (MODBUS RTU)
3
1
3
0
www.comfort-flex.com